beautypg.com

Viconics VWZS Integration Guide User Manual

Page 10

background image

10

Yellow device / node / controller have given out its 6 addresses to other devices in

building A.

Building B devices / nodes / controllers can only be connected through blue device /

nodes / controller due to maximum distance coverage.

Result:

Orange devices / nodes / controllers cannot join the ZigBee network.

Workaround to get orphan devices on the network:

Disconnect & bring one of building B device / node / controller & power it up in building

A until it joins the ZigBee network ( confirmed either at the Jace

– coordinator or using

the status LED on the wireless communication card of the device / node / controller.

When the device / node / controller has joined the network in building A and is added to

the Niagara database, bring it back into building B so it can propagate ZigBee
addresses to the other devices in building B.