Viconics VWZS Integration Guide User Manual
Page 54
54
Object Name
Object Type
Thermostat Range / Indexes
Minimum Supply Heat Setpoint
Numeric Writable
temperature,min=50,max=72
Mixed Air Setpoint
Numeric Writable
temperature,min=50,max=90
Occupied Cooling Setpoint
Numeric Writable
temperature,min=54,max=100
Occupied Heating Setpoint
Numeric Writable
temperature,min=40,max=90
Outdoor Temperature
Numeric Writable
temperature,min=-40,max=122
Outdoor Temperature
Numeric Writable
temperature,min=-40,max=150
Password
Numeric Writable
none,min=0,max=1000
PI Cooling Demand
Numeric Point
percent,min-0,max=100
PI Heating Demand
Numeric Point
percent,min-0,max=100
Powerup Delay
Numeric Writable
seconds,min=10,max=120
Return Air Temperature
Numeric Point
temperature,min=-40,max=122
Room Humidity
Numeric Writable
percent,min=0,max=100
Room Humidity
Numeric Writable
percent,min=5,max=90
Room Temperature
Numeric Writable
temperature,min=-40,max=122
RTC Comm Address
Numeric Writable
none,min=1,max=127
Standby Cooling Setpoint
Numeric Writable
temperature,min=54,max=100
Standby Heating Setpoint
Numeric Writable
temperature,min=40,max=90
Standby Time
Numeric Writable
hours,min=5.0,max=240.0
Static Pressure
Numeric Point
pascal,min=0,max=5000
Static Pressure Setpoint
Numeric Writable
pascal,min=0,max=5000
Supply Heat Lockout Temperature
Numeric Writable
temperature,min=-15,max=120
Supply PI Heat Demand
Numeric Point
percent,min=0,max=100
Supply RH
Numeric Point
percent,min=0,max=100
Supply Temperature
Numeric Point
temperature,min=-40,max=122
Supply Temperature
Numeric Point
temperature,min=-40,max=150
Unoccupied Cooling Setpoint
Numeric Writable
temperature,min=54,max=100
Unoccupied Heating Setpoint
Numeric Writable
temperature,min=40,max=90
Unoccupied Time
Numeric Writable
hours,min=0.0,max=240.0
Unoccupied Time
Numeric Writable
hours,min=5.0,max=240.0
Water Temperature
Numeric Point
temperature,min=-40,max=122
Weighted PI Cooling Demand
Numeric Point
percent,min-0,max=100
Weighted PI Heating Demand
Numeric Point
percent,min-0,max=100
** Room Temperature, Outdoor Temperature and Room Humidity need to have their Boolean
override counterpart object set to “Override” first if the present value needs to be written over
from the network. Ex To set a network present value on the numeric
“{Room Temperature”
numeric object, the
“
Room Temperature Override
”
Boolean object needs to be set from Normal to
Override. The controller local present value will then be derived from the wireless network
instead of the present value at the controller.