List of Property Enumeration Sets for BV Objects

Please refer to the specific installation guide of each controller for a detailed overview on each property listed

Object Name

Object Type

Thermostat Range / Indexes

AI1 Configuration

Boolean Writable

falseText=None,trueText=CO2

AO2 Lock Status

Boolean Point

falseText=Inactive,trueText=Active

AO2 RA/DA

Boolean Writable

falseText=Direct Acting,trueText=Reverse Acting

Auto Fan

Boolean Writable

falseText=Auto Speed,trueText=Auto Speed / Auto Demand

Auto Mode Enable

Boolean Writable

falseText=Disabled,trueText=Enabled

Aux Command

Boolean Writable

falseText=Off,trueText=On

Aux Contact

Boolean Writable

falseText=Normally Opened,trueText=Normally Closed

Aux Status

Boolean Point

falseText=Off,trueText=On

BI1 Status

Boolean Point

falseText=Deactivated,trueText=Activated

BI2 Status

Boolean Point

falseText=Deactivated,trueText=Activated

BO5 Contact Function

Boolean Writable

falseText=Normally Opened,trueText=Normally Closed

BO5 Lock Status

Boolean Point

falseText=Inactive,trueText=Active

BO5 Status

Boolean Point

falseText=Off,trueText=On

BO5 Time Base

Boolean Writable

falseText=15 Minutes,trueText=10 Seconds

Comfort Mode

Boolean Writable

falseText=Comfort,trueText=Economy

Compressor Auxiliary Lockout

Boolean Writable

falseText=Off,trueText=On

Config Motion Detection

Boolean Writable

falseText=No PIR,trueText=PIR Cover Present

Control Type

Boolean Writable

falseText=On/Off,trueText=Floating

Cool NO/NC

Boolean Writable

falseText=Normally Closed,trueText=Normally Openend

Cool Stages Lockout Status

Boolean Point

falseText=Off,trueText=On

Cooling Lockout Status

Boolean Point

falseText=Off,trueText=On

Cooling Valve Status

Boolean Point

falseText=Off,trueText=On

Dehumidification Lockout

Boolean Writable

falseText=Disabled,trueText=Enabled

Dehumidification Lockout Functions

Boolean Writable

falseText=Disabled,trueText=Enabled

Dehumidification Output Status

Boolean Point

falseText=Off,trueText=On

Dehumidification Status

Boolean Point

falseText=Off,trueText=On

DI Status

Boolean Point

falseText=Deactivated,trueText=Activated

DI1 Status

Boolean Point

falseText=Deactivated,trueText=Activated

DI2 Status

Boolean Point

falseText=Deactivated,trueText=Activated

Direct Reverse Acting

Boolean Writable

falseText=Direct Acting,trueText=Reverse Acting

Discharge Air Alarm

Boolean Point

falseText=Off,trueText=On

Discharge Temperature Alarm

Boolean Point

falseText=Off,trueText=On

Display Scale

Boolean Writable

falseText=C,trueText=F

Fan Control

Boolean Writable

falseText=Off,trueText=On

Fan Lock Alarm

Boolean Point

falseText=Off,trueText=On

Fan Options

Boolean Writable

falseText=On Heat,trueText=Auto Heat

Fan Purge Delay

Boolean Writable

falseText=Off,trueText=On

Filter Alarm

Boolean Point

falseText=Off,trueText=On

Frost Alarm

Boolean Point

falseText=Off,trueText=On

Frost Protection

Boolean Writable

falseText=Off,trueText=On

G Fan Status

Boolean Point

falseText=Off,trueText=On

Heat NO/NC

Boolean Writable

falseText=Normally Closed,trueText=Normally Openend

Heat Stages Lockout Status

Boolean Point

falseText=Off,trueText=On

Heating Lockout Status

Boolean Point

falseText=Off,trueText=On

Heating Valve Status

Boolean Point

falseText=Off,trueText=On