Objects Supported By Models: (VZ7000 Zoning Products)
Please refer to the specific installation guide of each controller for a detailed overview on each property listed.
Object Name
Object Type
Object Property
VZ7
2
0
0
F
5
x
0
0
W
VZ7
2
6
0
F
5
x
0
0
W
VZ7
2
6
0
C5
x
0
0
W
VZ7
6
5
6
B1
0
0
0
W
VZ7
6
5
6
R1
0
0
0
W
VZ7
6
5
6
H1
0
0
0
W
VZ7
6
5
6
F
1
0
0
0
W
VZ7
6
5
6
E
1
0
0
0
W
Outdoor Temperature Override
Boolean Writable
Present Value (R,W)
Occupancy Command
Enum Writable
Present Value (R,W)
Effective Occupancy
Enum Point
Present Value (R)
Occupied Cooling Setpoint
Numeric Writable
Present Value (R,W)
Occupied Heating Setpoint
Numeric Writable
Present Value (R,W)
Unoccupied Cooling Setpoint
Numeric Writable
Present Value (R,W)
Unoccupied Heating Setpoint
Numeric Writable
Present Value (R,W)
Temporary Occupancy Time
Enum Writable
Present Value (R,W)
Thermostat Model Number
Numeric Point
Present Value (R)
Module Firmware Version Number
Numeric Point
Present Value (R)
Thermostat Firmware Version
Number
Numeric Point
Present Value (R)
RTC Smart Recovery Active
Boolean Point
Present Value (R)
TRSS
NumericSpecial
Present Value (R)
CRSS
NumericSpecial
Present Value (R)
Heartbeat Delay
NumericNoStale
Present Value (R)
Room Temperature
Numeric Writable
Present Value (R,W)
Room Temperature Override
Boolean Writable
Present Value (R,W)
Outdoor Temperature
Numeric Writable
Present Value (R,W)
Standby Cooling Setpoint
Numeric Writable
Present Value (R,W)
Standby Heating Setpoint
Numeric Writable
Present Value (R,W)
PI Cooling Demand
Numeric Point
Present Value (R)
PI Heating Demand
Numeric Point
Present Value (R)
Weighted PI Cooling Demand
Numeric Point
Present Value (R)