BACNET NETWORK SETTINGS
Configuration parameters
default value
Significance and adjustments
COM address
Terminal Equipment Controller
networking address
Default value = 254
Range is: 0 to 254
For BACnet
®
MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet
®
communication for the Terminal
Equipment Controller.
Network units
Default value = Imperial
(Imperial): Network units shown as “imperial” units.
(Si): Network units shown as “international metric” units.
Network lang.
Default value = English
Choice of network language / object names that will be transmitted over
the network.
Other choices: (French) (Spanish).
Baud rate
Default value = Auto
(Auto): Will automatically detect the BACnet
®
MS/TP baud rate.
Other choices: (115200) (76800) (57600) (38400) (19200) (9600).
PARAMETER DETAILS
Indicates the controller
status on the network
Page 1 of 2
1/2 BACnet network
Baud rate
Auto
Network units
SI
Network lang.
English
BACnet status
Offline
COM address
254
"254" value will set BACnet
®
network "Offline". To activate
"Online", choose a different
value