PARAMETER DETAILS (CONT'D)

Configuration parameters
default value

Significance and adjustments

Pipe no.

Default is: 2.0 Pipes

System type installation: Number of pipes. Defines the type of system
installed.

Seq. operation

Default is: Heat

Selects the initial sequence of operation required by the installation type
and the application.

2 Pipes

4 Pipes

Cool

Cooling only

Cooling only

Heat

Heating only

Heating only

Ht-Cl

Cooling with electric reheat

Heating / Cooling

Ht-Rht

Heating with electric reheat

---

Reheat

Electric reheat only

---

For 2 Pipe output applications, the system access is limited if RUI 1 is

configured for local changeover COS, COC/NC or COC/NC. The current
water temperature detected by the RUI 1 then limits the system mode
available for the local configuration or network write.

For sequence “electric reheat”, set PulsedHt to "On" to enable pulsed

electric reheat applications with SC3400E & SC3404E.

Purge sample
Default is: 2 hrs

Time interval between valve samples. Will open valve for a short period
(adjusted by “Purge open” parameter to sample pipe temperature (to
decide between heating or cooling mode).

Adjustable for 0 to 4 hrs.

(0 = disable this function).

Purge open
Default is: 2 min

Time the valve will open to sample pipe temperature (to decide between

heating or cooling mode).

Adjustable for 1 to 3 min.