PARAMETER DETAILS (CONT'D)
Configuration parameters
default value
Significance and adjustments
Pipe no.
Default is: 2.0 Pipes
System type installation: Number of pipes. Defines the type of system
installed.
Seq. operation
Default is: Heat
Selects the initial sequence of operation required by the installation type
and the application.
2 Pipes
4 Pipes
Cool
Cooling only
Cooling only
Heat
Heating only
Heating only
Ht-Cl
Cooling with electric reheat
Heating / Cooling
Ht-Rht
Heating with electric reheat
---
Reheat
Electric reheat only
---
For 2 Pipe output applications, the system access is limited if RUI 1 is
configured for local changeover COS, COC/NC or COC/NC. The current
water temperature detected by the RUI 1 then limits the system mode
available for the local configuration or network write.
For sequence “electric reheat”, set PulsedHt to "On" to enable pulsed
electric reheat applications with SC3400E & SC3404E.
Purge sample
Default is: 2 hrs
Time interval between valve samples. Will open valve for a short period
(adjusted by “Purge open” parameter to sample pipe temperature (to
decide between heating or cooling mode).
Adjustable for 0 to 4 hrs.
(0 = disable this function).
Purge open
Default is: 2 min
Time the valve will open to sample pipe temperature (to decide between
heating or cooling mode).
Adjustable for 1 to 3 min.