PARAMETER DETAILS (CONT'D)

Configuration parameters
default value

Significance and adjustments

RBI 2

Remote Binary input

no.2 configuration

Default value = None

(None): No function will be associated with the input. Input can be used for
remote network monitoring.

(Filter): "Filter alarm" will be displayed on the Terminal Equipment Controller
LCD screen when the input is energized. It can be tied to a differential
pressure switch that monitor filters.

Contact opened = No alarm

Contact closed = Alarm displayed

(Service): "Service alarm" will be displayed on the Terminal Equipment
Controller LCD screen when the input is energized. It can be tied in to the
AC unit control card, which provides an alarm in case of malfunction.

Contact opened = No alarm

Contact closed = Alarm displayed

Occupancy cmd

(Loc Occ): Occupancy is determined by local sequences

(Occupied): Force occupied mode

(Unoccup): Force unoccupied mode