SETPOINT SETTINGS (CONT'D)
Configuration parameters
default value
Significance and adjustments
Default heat
Default value = 22.0 °C
( 73 °F )
This function is used for hospitality applications in stand-alone mode only.
When the devices is in deep unoccupied mode, any movement detected
by the PIR will reset the actual occupied set points to the “fresh room”
default setting.
This default setpoint is used to write to the “Heating setpoint” when the
thermostat goes to “Unoccupied” mode. Cooling setpoint will be set
according to the “Min. deadband”. 18.0 to 26.5 °C ( 65 to 80 °F ).
This parameter is only used when “Stand-by mode” = “Rel”.
Min. deadband
Default value = 1.5 °C
( 3.0 °F )
Minimum deadband value between the heating and cooling setpoints.
It will be applied only when any of the setpoints are modified.
Range is: 1.0 to 2.5 °C, 0.5 °C increments ( 2, 3, 4 or 5 °F,
1.0 °F increments ).
Max heating
Default value = 32.0 °C
( 90.0 °F )
Maximum occupied & unoccupied heating setpoint adjustment.
Range: 4.5 to 32.0 °C ( 40 to 90 °F ).
Min. cooling
Default value = 12.0 °C
( 54.0 °F )
Minimum occupied & unoccupied cooling setpoint adjustment.
Range: 12.0 to 37.5 °C ( 54 to 100 °F ).
Dehumidify
Default value = 50 % RH
Dehumidification setpoint. Used only if dehumidification sequence is
enabled:
Range is: 30-95% RH.
(Models with humidity sensor only).
PARAMETER DETAILS
12.0 C
2/2 Setpoints
Max. heating
Min. deadband
Default heat
26.0 C
Min. cooling
Dehumidify
1.5 C
32.0 C
50% RH
Parameter only displayed on
models with built in humidity
sensor.