CONFIGURATION PARAMETERS
PARAMETER DETAILS
Configuration parameters
default value
Significance and adjustments
BI 1
Binary input no.1 configuration
Default value = None
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Rem NSB): Remote NSB timer clock input. The scheduling will now be
set as per the binary input. It provides low cost setback operation via a dry
contact.
Contact opened = Occupied
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy functions using a
Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR function and configuration.
Application information and examples are available on document: APP-
PIR-Guide-Exx. This document will provide the installers and system
designers with detailed examples on applications, parameter configuration
information, sequence of operation, troubleshooting and diagnostic help
required for the proper usage of the PIR accessory covers.
(Window) EMS: Forces the system to disable any current heating or
cooling action by the Terminal Equipment Controller. The mode stays the
same and the current setpoints are the same Occupied setpoints. Only
the outputs are disabled. There is a Door/Window alarm displayed on the
Terminal Equipment Controller to indicate to the local tenant that the door/
window needs to be closed for cooling or heating to resume.
1/7 Configuration
RBI 2
RUI 1
BI 2
BI 1
None
None
None
None
Occupancy cmd
Loc occ.