Configuration parameters
default value

Significance and adjustments

Deh. max. cool.

Default value = 100 %

Maximum cooling valve position when dehumidification is enabled. This
can be used to balance smaller reheat loads installed in regards to the
capacity of the cooling coil.

Range is: 20 to 100 %.

(Models with humidity sensor only).

Deh. lockout

Default value: Enabled

Dehumidification lockout, typically toggled through the network.

This variable enables or disables dehumidification based on central
network requirements from the BAS front end.

Enabled = Dehumidification Authorized

Disabled = Dehumidification Not Authorized

(Models with humidity sensor only).

PARAMETER DETAILS (CONT'D)