CONFIGURATION PARAMETERS (CONT'D)

These parameters are model
dependent and may not appear
on certain models.

Configuration parameters
default value

Significance and adjustments

Standby time
Default 0.5 hours

Time delay between the moment where the PIR cover detected the
last movement in the area and the time which the Terminal Equipment
Controller stand-by setpoints become active.

Range is: 0.5 to 24.0 hours in 0.5 hours increments.

Unocc. time
Default 0.0 hours

Time delay between the moment where the Terminal Equipment Controller
toggles to stand-by mode and the time which the Terminal Equipment
Controller unoccupied mode and setpoints become active.

The factory value or 0.0 hours: Setting this parameter to its default value
of 0.0 hours disables the unoccupied timer. This prevents the Terminal
Equipment Controller to drift from stand-by mode to unoccupied mode
when PIR functions are used.

Range is: 0.0 to 24.0 hours in 0.5 hours increments.

Temp. occ. time
Default value = 2 hours

Temporary occupancy time with occupied mode setpoints when override
function is enabled.

When the Terminal Equipment Controller is in unoccupied mode, function
is enabled with either the menu or UI2 configured as remote override input.

Range is: 0 to 24 hours in 1 hour increments.

Deh. hysteresis
Default value = 5 % RH

Humidity control hysteresis. Used only if dehumidification sequence is
enabled:

Range is: 2 to 20% RH.

(Models with humidity sensor only).

PARAMETER DETAILS

3/7 Configuration

Temp. occ. time

Unocc. time

Standby time

2.0 hrs

0.0 hrs

0.5 hrs

Deh hysteresis

5.0% RH

Deh. max cool

100%

Deh. lockout

Enabled