beautypg.com

Carrier AQUAZONE PCV015-060 User Manual

Page 8

background image

8

Side to Back Discharge Conversion

1. Remove screws to free the top and discharge panels. See

Fig. 5.

2. Remove the access panel and set aside.
3. Lift the discharge panel from side of unit and rotate it to

back using care not to damage blower wiring.

4. Check blower wire routing and connections for undue

tension or contact with sheet metal edges. Re-route if

necessary.

5. Check refrigerant tubing for contact with other compo-

nents. Adjust if necessary.

6. Reinstall top panel using screws set aside in Step 1.

NOTE: Location for some screws at bottom of discharge panel

may have to be changed.

7. Manually spin fan wheel to check for obstructions.

Adjust for any obstruction found.

8. Replace access panel.

Back to Side Discharge Conversion — Follow instructions

above for Side to Back Discharge Conversion, noting the

panels would be reversed.

Step 4 — Mount the Unit

HORIZONTAL UNITS (50PCH) — Horizontal units should be

mounted using the factory-installed hangers. Proper attachment

of hanging rods to building structure is critical for safety. See

Fig. 2 and 7. Rod attachments must be able to support the

weight of the unit. See Table 1 for unit operating weights.

VERTICAL UNITS (50PCV) — Vertical units are available in

left or right return air configurations. See Fig. 3. Mount the unit

on a vibration absorption pad slightly larger than the entire base

to minimize vibration transmission. It is not necessary to mount

the unit on the floor. See Fig. 8.

NOTE: Some codes require the use of a secondary drain pan

under vertical units. Check local codes for more information.

Step 5 — Check Duct System —

Size the duct sys-

tem to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a ship-

ping support installed at the factory. This must be removed

before operating unit.
SOUND ATTENUATION — To eliminate the transfer of

vibration to the duct system, a flexible connector is recom-

mended for both discharge and return air duct connections on

metal duct systems. The supply and return plenums should in-

clude internal duct liner of fiberglass or be made of duct board

construction to maximize sound attenuation of the blower.

Installing the WSHP unit to uninsulated ductwork in an uncon-

ditioned space is not recommended since it will sweat and

adversely affect the unit’s performance.

To reduce air noise, at least one 90-degree elbow could be

included in the supply and return air ducts, provided system

performance is not adversely impacted. The blower speed can

also be changed in the field to reduce air noise or excessive air-

flow, provided system performance is not adversely impacted.
EXISTING DUCT SYSTEM — If the unit is connected to

existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to

handle the unit airflow. If the ductwork is too small,

install larger ductwork.

• Check existing ductwork for leaks and repair as

necessary.

NOTE: Local codes may require ventilation air to enter the

space for proper indoor air quality. Hard-duct ventilation may

be required for the ventilating air supply. If hard ducted venti-

lation is not required, be sure that a proper air path is provided

for ventilation air to unit to meet ventilation requirement of the

space.

Step 6 — Install Condensate Drain

HORIZONTAL UNITS (50PCH) — Slope the unit toward

the drain at a

1

/

4

in. drop at drain end. See Fig. 9. If it is not pos-

sible to meet the required pitch, install a condensate pump at

the unit to pump condensate to building drain.

Horizontal units are not internally trapped, therefore an ex-

ternal trap is necessary. Install each unit with its own individual

trap and means to flush or blow out the condensate drain line.

Do not install units with a common trap or vent. For typical

condensate connections see Fig. 10.
NOTE: Never use a pipe size smaller than the connection.
VERTICAL UNITS (50PCV) — Each unit uses a condensate

hose inside all cabinets as a trapping loop, therefore an external

trap is not necessary. See Fig. 11.

Fig. 7 — Horizontal Hanger Bracket

(Factory Installed)

COMPRESSOR

SECTION

AIR HANDLER

SECTION

a50-8489

Vibration
Absorption
Pad

Fig. 8 — 50PCV Units Mounted with

Vibration Absorption Pad

Fig. 9 — Horizontal Unit Pitch

1/4” Pitch for
Drainage

Drain Connection

Pitch Toward
Drain