HEATING CYCLE ANALYSIS

COOLING CYCLE ANALYSIS

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

FLOW RATE (GPM) x

TEMP. DIFF. (DEG. F) x

FLUID FACTOR* =

(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE

=

(DEG F)

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE

=

(DEG F)

*Use 500 for water, 485 for antifreeze.

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

F

F

AIR

COIL

F

PSI

WATER OUT

WATER IN

F

PSI

LOOK UP PRESSURE DROP IN TABLE 23
TO DETERMINE FLOW RATE

F

LIQUID LINE

PSI

F

SAT

a50-8445

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXP ANSION

VA LV E

°F

°F

AI R

COI L

°F

PSI

WA TER OUT

WA TER IN

°F

PSI

LOOK UP PRESSURE DROP IN T ABLE 23
TO DETERMINE FLOW RA TE

°F

LIQUID LIN E

PSI

°F

SA T

a50-8446