Table 30 — troubleshooting (cont) – Carrier AQUAZONE RVC User Manual
Page 42
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500007-01
Printed in U.S.A.
Form 50R-5SI
Pg 42
6-07
Replaces: 50R-4SI
Book 1
4
Tab
5a 5a
Copyright 2007 Carrier Corporation
Table 30 — Troubleshooting (cont)
LEGEND
RV — Reversing Valve
FAULT
HEATING
COOLING
POSSIBLE CAUSE
SOLUTION
Only Compressor Runs
X
X
Thermostat wiring
Check G wiring at heat pump. Jumper G and R for fan operation.
X
X
Fan motor relay
Jumper G and R for fan operation. Check for line voltage across BR
contacts.
Check fan power enable relay operation (if present).
X
X
Fan motor
Check for line voltage at motor. Check capacitor.
X
X
Thermostat wiring
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in test mode.
Unit Does Not Operate in
Cooling
X
Reversing valve
Set for cooling demand and check 24 VAC on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating engage and disengage RV coil voltage to push valve.
X
Thermostat setup
Check for 'O' RV setup not 'B'.
X
Thermostat wiring
Check O wiring at heat pump. Check RV to ensure the valve is chang-
ing over from heating and cooling modes. A 'click' should be heard
when the RV changes modes.
Insufficient Capacity/
Not Cooling or Heating
Properly
X
X
Dirty filter
Replace or clean.
X
Reduced or no airflow in
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 8-13.
X
Reduced or no airflow in
cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 8-13.
X
X
Leaky ductwork
Check supply and return air temperatures at the unit and at distant duct
registers if significantly different, duct leaks are present.
X
X
Low refrigerant charge
Check superheat and subcooling Table 21.
X
X
Restricted metering device
Check superheat and subcooling Table 21. Replace.
X
Defective reversing valve
Manually check the four-way valve to ensure all valves are operational.
X
X
Thermostat improperly
located
Check location and for air drafts behind thermostat.
X
X
Unit undersized
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
X
X
Scaling in water heat
exchanger
Check for scale (water deposits) and clean if necessary.
X
X
Inlet water too hot or cold
Check load, loop sizing, loop backfill, ground moisture.
High Head Pressure
X
Reduced or no airflow in
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 8-13.
X
Reduced or no water flow in
cooling
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate. See Table 20.
X
Inlet water too hot
Check load, loop sizing, loop backfill, ground moisture.
X
Air temperature out of range
in heating
Bring return air temperature within design parameters.
X
Scaling in water heat
exchanger
Check for scale (water deposits) and clean if necessary.
X
X
Unit overcharged
Check superheat and subcooling. Reweigh in charge.
X
X
Non-condensables in
system
Evacuate the refrigerant, recharge the system, and then weigh the new
refrigerant charge.
X
X
Restricted metering device
Check superheat and subcooling per Table 21. Replace.
Low Suction Pressure
X
Reduced water flow in
heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Water temperature out of
range
Bring water temperature within design parameters.
X
Reduced airflow in cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 8-13.
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within design
parameters.
X
X
Insufficient charge
Check for refrigerant leaks.
Low Discharge Air
Temperature in Heating
X
Too high airflow
Check blower Tables 8-13.
X
Poor performance
See 'Insufficient Capacity'.
High Humidity
X
Too high airflow
Check blower Tables 8-13.
X
Unit oversized
Recheck loads and sizing check sensible cooling load and heat pump
capacity.