Table 6 — 50RHR,RVR Electrical Data
LEGEND
*Size 006 is available in 50RHR units only.
50RHR,RVR
UNITS
VOLTS-PHASE
60 Hz
VOLTAGE
MIN/MAX
COMPRESSOR
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/HACR
RLA
LRA
006*
208/230-1
197/254
2.9
17.7
0.40
3.3
4.0
15
265-1
239/292
2.5
15.0
0.35
2.8
3.5
15
009
208/230-1
197/254
3.9
22.2
0.80
4.7
5.7
15
265-1
239/292
3.3
18.8
0.90
4.2
5.0
15
012
208/230-1
197/254
5.3
27.9
0.80
6.1
7.5
15
265-1
239/292
4.2
22.2
0.90
5.1
6.2
15
015
208/230-1
197/254
5.9
29.0
1.00
6.9
8.4
15
265-1
239/292
5.4
27.0
0.86
6.3
7.7
15
019
208/230-1
197/254
7.9
48.3
1.10
9.0
11.0
15
265-1
239/292
7.1
41.0
0.90
8.0
9.7
15
024
208/230-1
197/254
8.7
48.3
1.30
10.0
12.1
20
265-1
239/292
8.3
47.0
1.58
9.9
12.0
20
208/230-3
197/254
6.0
50.0
1.30
7.3
8.8
15
460-3
414/506
3.2
25.0
0.85
4.1
4.9
15
030
208/230-1
197/254
11.2
60.0
1.90
13.1
15.9
25
265-1
239/292
10.3
58.0
1.66
11.9
14.5
20
208/230-3
197/254
6.4
50.0
1.90
8.3
9.9
15
460-3
414/506
3.2
25.0
1.00
4.2
5.0
15
036
208/230-1
197/254
14.1
84.0
3.00
17.1
20.6
30
265-1
239/292
13.5
83.0
2.70
16.2
19.5
30
208/230-3
197/254
8.2
63.4
3.00
11.2
13.3
20
460-3
414/506
4.1
36.0
1.70
5.8
6.8
15
042
208/230-1
197/254
16.2
96.0
3.00
19.2
23.2
35
208/230-3
197/254
10.3
75.0
3.00
13.3
15.8
25
460-3
414/506
4.3
40.0
1.70
6.0
7.1
15
575-3
518/633
3.7
31.0
1.50
5.2
6.1
15
048
208/230-1
197/254
18.3
102.0
3.40
21.7
26.2
40
208/230-3
197/254
12.6
91.0
3.40
16.0
19.2
30
460-3
414/506
5.7
42.0
1.80
7.5
8.9
15
575-3
518/633
4.7
39.0
1.60
6.3
7.5
15
060
208/230-1
197/254
25.6
170.0
4.30
29.9
36.4
60
208/230-3
197/254
14.7
124.0
4.30
19.0
22.7
35
460-3
414/506
7.4
59.6
2.50
9.9
11.8
15
575-3
518/633
5.9
49.4
2.20
8.1
9.8
15
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps