Carrier AQUAZONE RVC User Manual
Page 20
20
*Optional wiring.
AL
— Alarm Relay Contacts
BM
— Blower Motor
BMC
— Blower Motor Capacitor
BR
— Blower Relay
CB
— Circuit Breaker
CC
— Compressor Contactor
CO
— Sensor, Condensate Overflow
COMPR — Compressor
FP1
— Sensor, Water Coil Freeze Protection
FP2
— Sensor, Air Coil Freeze Protection
HP
— High-Pressure Switch
JW1
— Jumper, Alarm
LOC
— Loss of Charge Pressure Switch
Fig. 20 — Typical Aquazone™ Deluxe D Control Wiring
LEGEND
MV
— Motorized Valve
NEC
— National Electrical Code
P1
— Field Wiring Terminal Block
RVS
— Reversing Valve Solenoid
TRANS — Transformer
TXV
— Thermostatic Expansion Valve
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 208 v (RED) lead for 208/3/60. For 230/3/60
switch RED and ORG leads at L1 and insulate RED lead.
4. FP1 thermistor provides freeze protection for water. When using anti-
freeze solutions, cut JW3 jumper.
5. Typical Aquazone thermostat wiring shown. Refer to thermostat installa-
tion instructions for wiring to the unit. Thermostat wiring must be Class 1
and voltage rating equal to or greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut AL2 dry
jumper and dry contact will be available between AL1 and
AL2.
7. Transformer secondary ground via control board standoffs
and screws to control box. (Ground available from top two
standoffs as shown.)
8. Blower motor is factory wired for medium and high speeds.
For any other combination of speeds, attach the lower speed
wire to fan speed relay N.O. wire.
a50-8161