beautypg.com

Carrier AQUAZONE RVC User Manual

Page 19

background image

19

*Optional wiring.

AL

Alarm Relay Contacts

BM

Blower Motor

BMC

Blower Motor Capacitor

BR

Blower Relay

CB

Circuit Breaker

CC

Compressor Contactor

CO

Sensor, Condensate Overflow

COMPR — Compressor
FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High-Pressure Switch

HWTS

High (Leaving) Water Temperature

Switch

JW1

Jumper, Alarm

NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 265 v (BRN) lead for 265/1/60 units, or

208 v (RED) lead for 208/1/60. For 230/1/60 switch RED and
ORG leads at L1 and insulate RED lead. Transformer is energy
limiting or may have circuit breaker.

4. FP1 thermistor provides freeze protection for water. When using

antifreeze solutions, cut JW3 jumper.

5. Typical Aquazone thermostat wiring shown. Refer to thermostat

installation instructions for wiring to the unit. Thermostat wiring
must be Class 1 and voltage rating equal to or greater than unit
supply voltage.

Fig. 19 — Typical Aquazone™ Complete C Control Wiring

LEGEND

LOC

Loss of Charge Pressure Switch

MV

Motorized Valve

NEC

National Electrical Code

P1

Field Wiring Terminal Block

PM

Performance Monitor

RV

Reversing Valve Coil

TRANS — Transformer
TXV

Thermostatic Expansion Valve

Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Temperature Switch

Thermistor

Ground

Wire Nut

6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper

and dry contact will be available between AL1 and AL2.

7. Transformer secondary ground via control board standoffs and

screws to control box. (Ground available from top two standoffs
as shown.)

8. For high or low speed remove BLU wire from BR ‘NO’

and replace with BLK or RED wire respectively. Tape off unused
terminal.

9. Both DIP switches need to be in the ON position.

a50-8160