beautypg.com

Antifreeze – Carrier AQUAZONE RVC User Manual

Page 35

background image

35

Table 22 — 50RHR,RVR Coaxial

Water Pressure Drop

*Size 006 available in 50RHR unit only.

Table 23 — 50RHS,RVS,RDS Coaxial

Water Pressure Drop

Table 24 — 50RHC,RVC Coaxial

Water Pressure Drop

*Size 006 available in 50RHC unit only.

†Size 041 available in 50RVC unit only.

Antifreeze —

In areas where entering loop temperatures

drop below 40 F or where piping will be routed through areas

subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze

agents. Freeze protection should be maintained to 15 F below

the lowest expected entering loop temperature. For example, if

the lowest expected entering loop temperature is 30 F, the leav-

ing loop temperature would be 22 to 25 F. Therefore, the freeze

protection should be at 15 F (30 F – 15 F = 15 F).

Calculate the total volume of fluid in the piping system. See

Table 25. Use the percentage by volume in Table 26 to deter-

mine the amount of antifreeze to use. Antifreeze concentration

should be checked from a well mixed sample using a hydrome-

ter to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1

factory setting (water) should be used to avoid freeze damage

to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should

be clipped on the control to select the low temperature (anti-

freeze 13 F) set point to avoid nuisance faults.

UNIT

50RHR,RVR

GPM

WATER TEMPERATURE (F)

30 F

50 F

70 F

90 F

Pressure Drop (psi)

006*

0.8

0.8

0.8

0.7

0.7

1.1

1.2

1.1

1.0

1.0

1.5

2.0

1.9

1.8

1.7

009

1.1

1.2

1.1

1.0

0.9

1.7

1.7

1.6

1.5

1.4

2.2

3.5

3.2

3.0

2.8

012

1.5

2.8

2.6

2.4

2.3

2.3

6.0

5.6

5.2

4.9

3.0

9.6

9.0

8.3

7.9

015

1.8

2.5

2.3

2.1

2.0

2.6

4.8

4.5

4.1

3.9

3.5

8.1

7.6

7.0

6.6

019

2.3

1.9

1.7

1.6

1.5

3.4

3.4

3.1

2.9

2.7

4.5

6.6

6.2

5.7

5.4

024

3.0

2.0

1.9

1.7

1.6

4.5

4.2

3.9

3.6

3.4

6.0

7.0

6.5

6.0

5.7

030

3.8

1.4

1.3

1.2

1.2

5.5

2.4

2.3

2.1

2.0

7.5

3.9

3.7

3.4

3.2

036

4.5

1.1

1.1

1.0

0.9

6.8

2.1

2.0

1.9

1.8

9.0

3.5

3.3

3.0

2.9

042

5.3

1.4

1.3

1.2

1.2

7.9

2.9

2.7

2.5

2.3

10.5

4.6

4.2

3.9

3.7

048

6.0

2.1

1.9

1.8

1.7

9.0

3.9

3.7

3.4

3.2

12.0

6.4

5.9

5.5

5.2

060

7.5

2.9

2.7

2.5

2.4

11.3

5.7

5.3

4.9

4.7

15.0

9.4

8.7

8.1

7.7

UNIT

50RHS,RVS,RDS

GPM

WATER TEMPERATURE (F)

30 F

50 F

70 F

90 F

Pressure Drop (psi)

015

1.8

0.6

0.5

0.5

0.5

2.8

1.0

0.9

0.8

0.8

3.8

1.5

1.4

1.3

1.2

018

2.2

0.7

0.7

0.6

0.6

3.5

1.3

1.2

1.1

1.1

4.5

1.8

1.8

1.6

1.5

024

3.0

0.6

0.6

0.5

0.5

4.5

1.1

1.1

1.0

0.9

6.0

1.8

1.7

1.5

1.5

030

3.7

0.8

0.8

0.7

0.7

5.5

1.6

1.4

1.3

1.3

7.5

2.6

2.4

2.2

2.1

036

4.5

1.3

1.2

1.1

1.1

7.0

2.1

1.9

1.8

1.7

9.0

3.9

3.7

3.4

3.2

042

5.2

1.6

1.5

1.4

1.3

8.0

3.2

3.0

2.8

2.6

10.5

5.1

4.7

4.4

4.1

048

6.0

2.1

1.9

1.8

1.7

9.0

3.9

3.7

3.4

3.2

12.0

6.4

5.9

5.5

5.2

060

7.5

1.1

1.0

1.0

0.9

11.3

2.2

2.1

1.9

1.8

15.0

3.6

3.4

3.1

3.0

070

9.0

1.5

1.4

1.3

1.2

13.5

3.0

2.8

2.6

2.5

18.0

5.0

4.7

4.3

4.1

UNIT

50RHC,RVC

GPM

WATER TEMPERATURE (F)

60 F

70 F

80 F

90 F

Pressure Drop (psi)

006*

0.9

0.7

0.7

0.7

0.6

1.1

1.2

1.2

1.2

1.1

1.7

1.9

1.9

1.8

1.8

2.0

2.9

2.8

2.7

2.6

009

1.1

2.4

2.3

2.3

2.2

1.7

3.1

3.0

2.9

2.8

2.3

4.0

3.9

3.8

3.7

3.0

5.4

5.3

5.1

4.9

012

1.5

2.3

2.2

2.1

2.1

2.3

4.4

4.3

4.2

4.0

3.0

6.4

6.2

6.0

5.8

4.0

13.3

12.9

12.6

12.2

018

2.3

2.0

2.0

1.9

1.8

3.5

3.1

3.0

2.9

2.8

4.5

4.2

4.1

3.9

3.8

6.0

5.9

5.7

5.6

5.4

024

3.0

2.0

1.9

1.8

1.8

4.5

3.9

3.7

3.6

3.5

6.0

6.4

6.2

6.0

5.8

8.0

10.6

10.3

10.0

9.7

030

3.8

1.5

1.5

1.4

1.4

5.5

2.7

2.6

2.5

2.4

7.5

4.3

4.2

4.1

3.9

10.0

6.9

6.7

6.5

6.3

036

4.5

1.7

1.7

1.6

1.6

6.8

3.2

3.1

3.0

2.9

9.0

5.0

4.9

4.8

4.6

12.0

8.2

7.9

7.7

7.5

041†

5.3

0.9

0.9

0.9

0.9

7.9

2.2

2.1

2.1

2.0

10.5

4.0

3.9

3.8

3.6

13.0

6.2

6.0

5.8

5.7

042

5.3

1.0

1.0

1.0

0.9

8.0

2.6

2.6

2.5

2.4

11.0

5.3

5.1

4.9

4.8

14.0

8.7

8.5

8.2

8.0

048

6.0

1.2

1.2

1.2

1.1

9.0

2.9

2.8

2.7

2.6

12.0

5.3

5.1

4.9

4.8

16.0

9.5

9.2

8.9

8.6

060

7.5

4.4

4.2

4.1

4.0

11.3

7.6

7.3

7.1

6.9

15.0

11.4

11.1

10.8

10.4

20.0

17.6

17.1

16.6

16.1

IMPORTANT: All alcohols should be pre-mixed and

pumped from a reservoir outside of the building or

introduced under water level to prevent fuming.

This manual is related to the following products: