AIR COIL — To obtain maximum performance, clean the air

coil before starting the unit. A ten percent solution of dish-

washer detergent and water is recommended for both sides of

the coil. Rinse thoroughly with water.

PSC (Permanent Split Capacitor) Blower
Speed Selection —

All water source heat pumps are

factory set to deliver rated airflow at nominal static (0.15 in.

wg) on medium speed. Where higher static is needed, high

speed can be utilized (0.4 to 0.5 in. wg). Low speed will

deliver approximately 85% of rated airflow (0.10 in. wg). The

PSC blower fan speed can be changed on all units by swapping

wires connected to the relay contacts that control the fan. See

Fig. 27.
FOR 50RHR,RVR,RHS,RVS AND RDS UNITS — On the

control, the black wire is connected to High, blue wire is

connected to Medium and red wire is connected to Low. See

Fig. 19-22.
NOTE: Available airflows for all units are shown in Tables 8-13.
FOR 50RHC,RVC UNITS — The PSC blower fan speed

can be changed by moving the blue wire on the fan motor ter-

minal block to the desired speed as shown in Fig. 27. The

50RHC,RVC units are designed to deliver rated airflow at

nominal static (0.15 in. wg) on medium speed (factory setting)

and rated airflow at a higher static (0.4 to 0.5 in. wg) on high

speed for applications where higher static is required. Low

speed will deliver approximately 85% of rated airflow at

0.10 in. wg. An optional ‘High Static’ blower is available by

using the special option code in the model nomenclature.

Table 8 — 50RHR,RVR Blower Performance

LEGEND

*Size 006 available in 50RHR units only.

NOTES:

1. Units factory shipped on medium speed. Other speeds require

field selection.

2. All airflow is rated on 208 v operating with wet coil and clean air

filter.

3. All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed.
4. Only two-speed fan (H & M) available on 575-v units.

50RHR,RVR

UNITS

RATED

CFM

MIN

CFM

FAN

SPEED

AIRFLOW (Cfm)

External Static Pressure (in. wg)

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

006*

200

150

HI

300

290

280

270

260

250

240

230

210

190

160

110

MED

240

230

220

210

200

190

180

160

140

130

110

LO

220

210

200

200

190

180

160

150

130

130

009

300

225

HI

450

440

430

420

400

390

370

350

320

310

300

230

MED

410

400

390

380

360

350

340

330

310

290

270

LO

370

360

350

340

320

320

310

300

280

260

240

012

375

300

HI

470

460

450

440

430

420

400

390

380

370

350

330

290

MED

410

400

380

370

360

360

350

340

330

320

310

290

LO

340

330

320

320

310

310

300

300

290

290

015

500

375

HI

750

730

710

700

680

660

630

600

570

540

500

400

MED

660

640

620

610

590

570

550

530

500

470

440

370

LO

580

570

550

540

520

500

480

460

430

400

370

019

600

450

HI

850

820

790

770

740

710

670

640

600

560

520

450

MED

700

680

660

640

620

590

560

530

500

470

440

LO

600

580

560

540

510

490

460

460

024

800

600

HI

980

950

920

890

860

830

790

760

720

680

640

540

MED

850

830

800

770

740

720

690

660

620

580

540

460

LO

700

680

660

650

630

610

590

560

530

500

470

030

1000

750

HI

1330 1300 1260 1230 1190 1150 1100 1050 1000

960

920

830

MED

1210 1190 1160 1130 1100 1050 1000

970

930

880

830

720

LO

1050 1030 1010

980

950

920

890

850

810

770

730

036

1200

900

HI

1580 1540 1500 1470 1440 1410 1370 1330 1280 1240 1200 1090

940

MED

1400 1370 1340 1310 1280 1250 1220 1190 1150 1100 1050

920

LO

1100 1080 1060 1040 1010

980

950

920

890

890

042

1400

1050

HI

1790 1760 1730 1700 1660 1630 1590 1550 1510 1480 1440 1370 1270 1120

MED

1500 1490 1470 1450 1420 1400 1380 1350 1320 1300 1270 1180 1070

LO

1110 1100 1090 1080 1060 1050 1040

048

1600

1200

HI

1910 1880 1840 1800 1750 1730 1700 1650 1600 1540 1480 1380 1300 1180

MED

1830 1790 1740 1700 1660 1620 1570 1540 1500 1450 1400 1320 1210 1120

LO

1700 1670 1640 1600 1560 1530 1490 1460 1430 1390 1340 1250 1170

High Static

048

1600

1200

HI

2180 2140 2090 2060 2030 1990 1940 1870 1800 1750 1690 1580 1440 1270

990

MED

2080 2050 2020 1970 1920 1870 1820 1740 1650 1640 1620 1530 1320 1220

910

LO

1990 1950 1910 1880 1840 1810 1770 1710 1650 1620 1580 1460 1340 1180

060

2000

1500

HI

2230 2220 2200 2160 2120 2090 2060 2040 2010 1990 1960 1880 1790 1660

MED

2040 2020 1990 1970 1940 1920 1890 1860 1830 1810 1780 1710 1620

LO

1840 1830 1810 1800 1780 1760 1730 1700 1670 1640 1600 1510

Shaded areas are below minimum CFM. This data is
provided for troubleshooting information only.

CFM — Cubic Feet Per Minute

CONNECT THE BLUE WIRE TO:

FAN MOTOR

MEDIUM FACTORY SETTING

H FOR HIGH SPEED FAN
M FOR MEDIUM SPEED FAN
L FOR LOW SPEED FAN

H

M

L

BLU

Fig. 27 — 50RHC,RVC Blower Speed Selection

This manual is related to the following products: