FIELD SELECTABLE INPUTS

Jumpers and DIP (dual in-line package) switches on the

control board are used to customize unit operation and can be

configured in the field.

C Control Jumper Settings (See Fig. 19)

WATER COIL FREEZE PROTECTION (FP1) LIMIT

SETTING — Select jumper 3, (JW3-FP1 Low Temp) to

choose FP1 limit of 10 F or 30 F. To select 30 F as the limit,

DO NOT clip the jumper. To select 10 F as the limit, clip the

jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-

TING — Select jumper 2 (JW2-FP2 Low Temp) to choose

FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT

clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2

Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)

or to remain as a dry contact (no connection). To connect AL2

to R, do not clip the jumper. To set as dry contact, clip the

jumper.

C Control DIP Switches —

The C Control has 1 DIP

switch block with two switches. See Fig. 19.
PERFORMANCE MONITOR (PM) — DIP switch 1 will

enable or disable this feature. To enable the PM, set the switch

to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor

delay. Set DIP switch to OFF for stage 2 in which the compres-

sor will have a 3-second delay before energizing.
NOTE: The alarm relay will not cycle during Test mode if

switch is set to OFF, stage 2.

D Control Jumper Settings (See Fig. 20)

WATER COIL FREEZE PROTECTION (FP1) LIMIT

SETTING — Select jumper 3, (JW3-FP1 Low Temp) to

choose FP1 limit of 10 F or 30 F. To select 30 F as the limit,

DO NOT clip the jumper. To select 10 F as the limit, clip the

jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-

TING — Select jumper 2 (JW2-FP2 Low Temp) to choose

FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT

clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2

Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)

or to remain as a dry contact (no connection). To connect AL2

to R, do not clip the jumper. To set as dry contact, clip the

jumper.
LOW PRESSURE SETTING — The D Control can be con-

figured for Low Pressure Setting (LP). Select jumper 1 (JW1-

LP Norm Open) for choosing between low pressure input nor-

mally open or closed. To configure for normally closed opera-

tion, do not clip the jumper. To configure for normally open op-

eration, clip the jumper.

D Control DIP Switches —

The D Control has 2 DIP

switch blocks. Each DIP switch block has 8 switches and is

labeled either S1 or S2 on the circuit board. See Fig. 20.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers

the following options for D Control configuration:
Performance Monitor (PM) — Set switch 1 to enable or dis-

able performance monitor. To enable the PM, set the switch to

ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation — Switch 2 will en-

able or disable compressor relay staging operation. The com-

pressor relay can be set to turn on with stage 1 or stage 2 call

from the thermostat. This setting is used with dual stage units

(units with 2 compressors and 2 D controls) or in master/slave

applications. In master/slave applications, each compressor and

fan will stage according to its switch 2 setting. If switch is set to

stage 2, the compressor will have a 3-second delay before ener-

gizing during stage 2 demand.
NOTE: If DIP switch is set for stage 2, the alarm relay will not

cycle during Test mode.
Heating/Cooling Thermostat Type — Switch 3 provides selec-

tion of thermostat type. Heat pump or heat/cool thermostats

can be selected. Select OFF for heat/cool thermostats. When in

heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for

cooling stage 2, W1 is used for heating stage 1 and O/W2 is

used for heating stage 2. Select ON for heat pump applications.

In heat pump mode, Y1 used is for compressor stage 1, Y2 is

used for compressor stage 2, W1 is used for heating stage 3 or

emergency heat, and O/W2 is used for RV (heating or cooling)

depending upon switch 4 setting.
O/B Thermostat Type — Switch 4 provides selection for heat

pump O/B thermostats. O is cooling output. B is heating out-

put. Select ON for heat pumps with O output. Select OFF for

heat pumps with B output.
Dehumidification Fan Mode — Switch 5 provides selection

of normal or dehumidification fan mode. Select OFF for dehu-

midification mode. The fan speed relay will remain OFF dur-

ing cooling stage 2. Select ON for normal mode. The fan speed

relay will turn on during cooling stage 2 in normal mode.
Switch 6 — Not used.
Boilerless Operation — Switch 7 provides selection of boiler-

less operation and works in conjunction with switch 8. In

IMPORTANT: Jumpers and DIP switches should only

be clipped when power to control board has been turned

off.

Table 13 — 50RHS, RVS Blower Performance with HWR

LEGEND

COIL FACE

VELOCITY (FPM)

50RHS, RVS WITH REHEAT ESP LOSS

50RHS, RVS

015, 018 (in. wg)

50RHS, RVS

024, 030 (in. wg)

50RHS, RVS

036 (in. wg)

50RHS, RVS

042, 048 (in. wg)

50RHS, RVS

060 (in. wg)

50RHS, RVS

070 (in. wg)

200

0.040

0.037

0.033

0.031

0.028

0.026

250

0.059

0.052

0.046

0.042

0.038

0.034

300

0.088

0.077

0.066

0.059

0.051

0.044

350

0.131

0.113

0.096

0.085

0.073

0.061

400

0.203

0.181

0.160

0.145

0.131

0.117

450

0.258

0.242

0.226

0.215

0.205

0.194

500

0.375

0.360

0.345

0.335

0.326

0.316

ESP

— External Static Pressure

HWR — Hot Water Reheat