beautypg.com

Unit start-up heating mode, Flow regulation, Flushing – Carrier AQUAZONE RVC User Manual

Page 34

background image

34

Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the

cooling cycle. Allow 5 minutes between tests for the pressure

or reversing valve to equalize.

1. Turn thermostat to lowest setting and set thermostat

switch to HEAT position.

2. Slowly turn the thermostat to a higher temperature until

the compressor activates.

3. Check for warm air delivery at the unit grille within a few

minutes after the unit has begun to operate.

4. Check the temperature of both supply and discharge wa-

ter. Compare to Table 21. If temperature is within range,

proceed. If temperature is outside the range, check the

heating refrigerant pressures in Table 21.

5. Once the unit has begun to run, check for warm air deliv-

ery at the unit grille.

6. Check air temperature rise across the coil when compres-

sor is operating. Air temperature rise should be between

20 and 30 F after 15 minutes at load.

7. Check for vibration, noise and water leaks.

Flow Regulation —

Flow regulation can be accom-

plished by two methods. Most water control valves have a flow

adjustment built into the valve. By measuring the pressure drop

through the unit heat exchanger, the flow rate can be deter-

mined. See Tables 22-24. Adjust the water control valve until

the flow of 1.5 to 2 gpm is achieved. Since the pressure con-

stantly varies, two pressure gages may be needed in some

applications.

An alternative method is to install a flow control device.

These devices are typically an orifice of plastic material de-

signed to allow a specified flow rate that are mounted on the

outlet of the water control valve. Occasionally these valves

produce a velocity noise that can be reduced by applying some

back pressure. To accomplish this, slightly close the leaving

isolation valve of the well water setup.

Flushing —

Once the piping is complete, units require final

purging and loop charging. A flush cart pump of at least 1.5 hp

is needed to achieve adequate flow velocity in the loop to purge

air and dirt particles from the loop. Flush the loop in both

directions with a high volume of water at a high velocity. Fol-

low the steps below to properly flush the loop:

1. Verify power is off.
2. Fill loop with water from hose through flush cart before

using flush cart pump to ensure an even fill. Do not allow

the water level in the flush cart tank to drop below the

pump inlet line to prevent air from filling the line.

3. Maintain a fluid level in the tank above the return tee to

avoid air entering back into the fluid.

4. Shutting off the return valve that connects into the flush

cart reservoir will allow 50 psi surges to help purge air

pockets. This maintains the pump at 50 psi.

5. To purge, keep the pump at 50 psi until maximum pump-

ing pressure is reached.

6. Open the return valve to send a pressure surge through

the loop to purge any air pockets in the piping system.

7. A noticeable drop in fluid level will be seen in the flush

cart tank. This is the only indication of air in the loop.

NOTE: If air is purged from the system while using a 10 in.

PVC flush tank, the level drop will only be 1 to 2 in. since

liquids are incompressible. If the level drops more than this,

flushing should continue since air is still being compressed in

the loop. If level is less than 1 to 2 in., reverse the flow.

8. Repeat this procedure until all air is purged.
9. Restore power.

Antifreeze may be added before, during or after the flushing

process. However, depending on when it is added in the

process, it can be wasted. Refer to the Antifreeze section for

more detail.

Loop static pressure will fluctuate with the seasons. Pres-

sures will be higher in the winter months than during the

warmer months. This fluctuation is normal and should be con-

sidered when charging the system initially. Run the unit in

either heating or cooling for several minutes to condition the

loop to a homogenous temperature.

When complete, perform a final flush and pressurize the

loop to a static pressure of 40 to 50 psi for winter months or 15

to 20 psi for summer months.

After pressurization, be sure to remove the plug from the

end of the loop pump motor(s) to allow trapped air to be

discharged and to ensure the motor housing has been flooded.

Be sure the loop flow center provides adequate flow through

the unit by checking pressure drop across the heat exchanger.

Compare the results to the data in Tables 22-24.

Table 21 — Typical Unit Operating Pressures and Temperatures

LEGEND

To avoid possible injury or death due to electrical shock,

open the power supply disconnect switch and secure it in

an open position before flushing system.

ENTERING

WATER

TEMP (F)

(EWT)

GPM/

TON

COOLING

HEATING

Suction

Pressure

(psig)

Discharge

Pressure

(psig)

Super-

heat

(F)

Sub-

cooling

(F)

Water

Temp

Rise

(F)

Air

Temp

Drop (F)

DB

Suction

Pressure

(psig)

Discharge

Pressure

(psig)

Super-

heat (F)

Sub-

cooling

(F)

Water

Temp

Drop (F)

DB

Air

Temp

Rise (F)

30

1.5

75-85

90-105

25-40

12-20

21-24

21-26

34- 39

167-186

12-16

1-4

7.6- 8.4

14-20

2.3

74-84

80- 95

25-40

11-18

13-16

21-26

37- 43

172-191

12-16

1-4

4.8- 5.6

16-22

3.0

73-83

70- 85

25-40

10-16

6-11

21-26

40- 46

177-196

12-16

1-4

3.4- 4.2

16-22

50

1.5

75-85

125-155

12-20

10-18

20-23

20-25

50- 60

180-210

10-17

1-5

10.8-11.9

23-29

2.3

74-84

120-142

12-20

9-16

12-15

20-25

53- 62

185-215

10-17

1-5

6.7- 8.1

24-30

3.0

73-83

115-138

12-20

8-14

8-12

20-25

55- 65

190-220

10-17

1-5

5.1- 5.9

25-31

70

1.5

75-85

179-198

9-16

8-15

19-22

19-24

71- 82

205-230

14-19

1-5

14.0-15.2

28-34

2.3

74-84

168-186

9-16

8-14

12-17

19-24

73- 85

210-238

14-19

1-5

9.0-10.2

30-37

3.0

73-83

158-175

9-16

8-12

7-12

19-24

76- 88

215-242

14-19

1-5

6.7- 7.9

31-38

90

1.5

75-85

229-251

9-17

8-15

18-21

17-23

85- 95

220-260

18-28

2-5

14.4-16.6

32-39

2.3

74-84

218-241

9-17

8-14

10-14

17-23

90-100

225-265

18-28

2-5

10.8-12.4

33-41

3.0

73-83

208-230

9-17

8-12

6-11

17-23

95-105

230-270

18-28

2-5

7.2- 8.3

35-42

110

1.5

77-87

280-320

8-15

10-25

17-20

15-20

2.3

76-86

270-310

8-15

10-24

9-13

15-20

3.0

75-85

260-300

8-15

10-22

5-10

15-20

DB

Dry Bulb

EAT

Entering Air Temperature

NOTES:

1. Based on nominal 400 cfm per ton airflow, 70 F EAT heating and 80/67 F

EAT cooling.

2. Cooling air and water numbers can vary greatly with changes in humidity.
3. Subcooling is based upon the head pressure at compressor service port.
4. Unit should not be operated in heating mode with an EWT of 110.

This manual is related to the following products: