Typical wiring diagrams -- pages 13 - 16 – Reznor BE Unit Installation Manual User Manual

Page 14

background image

Form RZ-NA-I-FE/BE, Mfg P/N 98807 Rev 10, Page 13

2

4

CONTACTS

VENTER RELAY

OPTIONAL

S/W SWITCH

FAN CONTROL

BK

BK

BK

BK

BK

BK

BK

L1

(HOT)

BK

R

VENTER MOTOR

BK

BR

GROUND TERMINAL

(TERMINAL STRIP)

L2

(COM)

115/1/60, 208/1/60 OR 230/1/60

3

1

VENTER RELAY COIL

BL

BR

BR

R

SET ANTICIP

AT

OR A

T 0.8 AMPS

W

.R 1C30-339 THERMOST

AT W-S23-6 SUBBASE

W

R

W

PRESSURE

SWITCH

Y

Y

Y

Y

LIMIT

CONTROL

Y

GRND.

RECYCLE

G67BG-5

OR

LOCKOUT

IGNITION

CHASSIS GRND.

CONTROLLER

G770NGC-4

1

3

2

4

W

PROBE

GRND

IGNITOR

STRIP

FLAME SENSING

BK

AL

TERNA

TE HONEYWELL

REDUNDANT GAS V

A

LV

E

BL

PILOT

OR PV

TH-TR

TH OR

MV

PV-MV

TR OR

MAIN

PILOT

W

.R. OR ROBER

TSHA

W

REDUNDANT GAS V

AL

VE

P

MAIN

M

C

BR

BR

BL

BL

R

BK

FIELD WIRING

TERMINAL STRIP

FACT

OR

Y WIRING

W

W

W

BK

BK

BR

BR

BK

G

GRD

CONTROL

BK

R

24V

LINE VOLT

BR

R

TRANSFORMER

Y

BK

FAN MOTOR

BK

BK

FE 25-400 OPT. AH2/AH3 WD #97302 REV #8

NOTES

1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS:

THERMOSTAT

2. THE FOLLOWING CONTROLS ARE FACTORY INSTALLED OPTIONS:

S/W SWITCH

3. DOTTED WIRING INSTALLED BY OTHERS.

4. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE APPLIANCE MUST BE

REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE

RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR SENSOR LEAD AND

LIMIT WIRING WHICH MUST BE 150 DEGREES C.

5. USE #18 GA WIRE FOR ALL WIRING EXCEPT FAN MOTOR CIRCUIT.

6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE

DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.

8. SEE INSTALLATION INSTRUCTIONS FOR GREATER DETAIL.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

ON 115V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

7. ON 230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

FOR 115V. UNITS USE BLACK AND YELLOW LEADS.

OPERATING SEQUENCE

1. SET THERMOSTAT AT LOWEST SETTING.

2. TURN ON MAIN AND PLOT MANUAL GAS VALVES.

3. TURN ON POWER TO UNIT.

5. THERMOSTAT CALLS FOR HEAT ENERGIZING THE VENTER MOTOR.

6. VENTER PRESSURE SWITCH CLOSES FIRING UNIT AT FULL RATE AFTER PILOT

8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION THE SAFETY SWITCH

CLOSES THE MAIN VALVE AND RECYCLES THE SPARK GAP. ON UNITS EQUIPPED

WITH THE G77ONGC-4 LOCKOUT CONTROL, IF PILOT IS NOT ESTABLISHED WITHIN 120

SECONDS (APPROX.) UNIT LOCKS OUT AND THE UNIT MUST BE RESET BY

INTERRUPTING POWER TO CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).

4. SET THERMOSTAT AT DESIRED SETTING.

PROVING SEQUENCE.

7. FAN CONTROL SENSES HEAT EXCHANGER TEMPERATURE, ENERGIZING THE

FAN MOTOR.

OPTIONAL FACTORY WIRING

FACTORY WIRING
FIELD WIRING

WIRE NUT

CRIMP TERMINAL

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

TYPICAL WIRING DIAGRAMS -- Pages 13 - 16

CAUTION: If any of the original wire as supplied with
the appliance must be replaced, it must be replaced
with wiring material having a temperature rating of at
least 105°C, except for limit control and sensor lead
wires which must be 150°C. See Hazard Levels, page
2.

Field Control Wiring Length and Gauge

Total Wire

Distance from

MinimumRecommended

Length

Unit to Control

Wire Gauge

150' (45.7 m)

75' (22.9 m)

#18 gauge

250' (76.2 m)

125' (38.1 m)

#16 gauge

350' (106.7 m)

175' (53.3 m)

#14 gauge

Fan-Type, Power-Vented Model with Intermittent Spark Pilot, Single-Stage Heating,
Natural or Propane