Form RZ-NA-I-FE/BE, Mfg P/N 98807, Rev 10, Page 14

Blower-Type, Power-Vented Model Sizes 25-100 with Intermittent Spark Pilot, Single-Stage Heating,
Natural or Propane, Direct Drive

OPERATING SEQUENCE

1. SET THERMOSTAT AT LOWEST SETTING.

2. TURN ON MAIN AND PILOT MANUAL GAS VALVES.

3. TURN ON POWER TO UNIT.

5. THERMOSTAT CALLS FOR HEAT ENERGIZING THE VENTER MOTOR.

6. VENTER PRESSURE SWITCH CLOSES FIRING UNIT AT FULL RATE AFTER PILOT

8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION THE SAFETY SWITCH

CLOSES THE MAIN VALVE AND RECYCLES THE SPARK GAP. ON UNITS EQUIPPED

WITH THE G77ONGC-4 LOCKOUT CONTROL, IF PILOT IS NOT ESTABLISHED WITHIN 120

SECONDS (APPROX.) UNIT LOCKS OUT AND THE UNIT MUST BE RESET BY

INTERRUPTING POWER TO CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).

4. SET THERMOSTAT AT DESIRED SETTING.

PROVING SEQUENCE.

7. FAN CONTROL SENSES HEAT EXCHANGER TEMPERATURE, ENERGIZING THE

BLOWER MOTOR.

NOTES

1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS:

THERMOSTAT

2. THE FOLLOWING CONTROLS ARE FACTORY INSTALLED OPTIONS:

S/W SWITCH AND S/W RELAY

3. DOTTED WIRING INSTALLED BY OTHERS.

4. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE APPLIANCE MUST BE

REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE

RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR SENSOR LEAD AND

LIMIT WIRING WHICH MUST BE 150 DEGREES C.

5. USE #14 GA WIRE FOR BLOWER MOTOR CIRCUIT WIRING ON UNIT.

6. USE #18 GA WIRE FOR ALL WIRING EXCEPT BLOWER MOTOR CIRCUIT.

7. LINE AND BLOWER MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE

DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.

9. SEE INSTALLATION INSTRUCTIONS FOR GREATER DETAIL.

B 50 USE BLACK MOTOR LEAD, CAP BLUE AND RED, OR USE BLUE MOTOR LEAD, CAP

8. THREE SPEED MOTOR CONNECTIONS ARE AS FOLLOWS:

BLACK AND RED

CAP BLACK AND RED, OR USE RED MOTOR LEAD, CAP BLACK AND BLUE

B 100-75 USE BLACK MOTOR LEAD, CAP BLUE AND RED, OR USE BLUE MOTOR LEAD,

B 25 USE BLUE MOTOR LEAD, CAP BLACK AND RED, OR USE BLUE MOTOR LEAD, CAP

BLACK AND RED

WIRE NUT

FIELD WIRING

OPTIONAL FACTORY WIRING

FACTORY WIRING

CRIMP

TERMINAL

2

4

VENTER CONTACTS

S/W RELAY

4

CONTACTS

2

FAN CONTROL

BK

BK

BK

BL/BK

BK

BK

BK

L1

(HOT)

BK

VENTER MOTOR

BK

W

S/W

RELAY COIL

BR

PR

BR

GROUND TERMINAL

(TERMINAL STRIP)

L2

(COM)

115/1/60

1

3

3

1

VENTER RELAY COIL

BL

BR

BR

BR

R

SET ANTICIP

AT

OR A

T 0.8 AMPS

W

.R 1C30-339 THERMOST

AT

W-S23-6 SUBBASE

W

R

W

PRESSURE

SWITCH

Y

Y

Y

Y

LIMIT

CONTROL

Y

GRND.

RECYCLE

G67BG-5

OR

LOCKOUT

IGNITION

CHASSIS GRND.

CONTROLLER

G770NGC-4

1

3

2

4

W

PROBE

GRND

IGNITOR

STRIP

FLAME SENSING

BK

AL

TERNA

TE HONEYWELL

REDUNDANT GAS V

A

LV

E

BL

PILOT

OR PV

TH-TR

TH OR

MV

PV-MV

TR OR

MAIN

PILOT

W

.R. OR ROBER

TSHA

W

REDUNDANT GAS V

A

LV

E

P

MAIN

M

C

BR

BR

BL

BK

BL

R

PR

BK

FIELD WIRING

TERMINAL STRIP

FACT

OR

Y WIRING

W

W

W

BK

BK

BR

BR

BK

G

GRD

CAPACITOR

BL (MEDIUM)

BK (HIGH)

R (LOW)

W

GR

GRD

BLOWER MOTOR

THREE SPEED

BR

BR

BE 25-100 (DIRECT DRIVE) WD# 100565 REV#4

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

CONTROL

BK

R

24V

115 VOLT

BR

TRANSFORMER

Y

BK

BK

S/W SWITCH

OPTIONAL

R

Model
S ize
S peed

*M edium Low

*High M edium High *M edium Low

*High M edium Low

Use these
Two Motor
Wires

*Blue and

White

Red

and

White

*Black

and

White

Blue and

White

Black

and

White

*Blue and

White

Red

and

White

*Black

and

White

Blue and

White

Red

and

White

*Factory-wired speed

25

50

75

100

This manual is related to the following products: