beautypg.com

Gas piping and pressures, Venting (cont'd), Manifold or orifice pressure settings – Reznor BE Unit Installation Manual User Manual

Page 11

background image

Form RZ-NA-I-FE/BE, Mfg P/N 98807, Rev 10, Page 10

11. Gas Piping and Pressures

WARNING

This appliance is equipped for a maximum gas
supply pressure of 1/2 pound, 8 ounces, or 14
inches water column. Supply pressure higher than
1/2 pound requires installation of an additional
service regulator external to the unit.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and
manual valve from the gas supply line which is to be tested.
Cap or plug the supply line.

Test Pressures Below 1/2 PSI: Before testing, close the manual

valve on the heater.

All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI/Z223.1a (latest edition) or CAN/CGA-
B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation
should conform with good practice and with local codes.

Unit heaters for natural gas are orificed for operation with gas having a
heating value of 1000 (+ or - 50) BTUH per cubic ft. If the gas at the
installation does not meet this specification, consult the factory for
proper orificing.

Pipe joint compounds (pipe dope) shall be resistant to the action
of liquefied petroleum gas or any other chemical constituents of
the gas being supplied.

Install a ground joint union and manual shut-off valve upstream of the
unit control system, as shown in Figure 11. The 1/8" plugged tapping in
the shut-off valve provides connection for supply line pressure test
gauge. The National Fuel Gas Code requires the installation of a trap
with a minimum 3" drip leg. Local codes may require a minimum drip
leg longer than 3" (typically 6").

Gas connection sizes are included in the Dimensional Tables in Para-
graph 3. After all connections are made, disconnect the pilot supply at
the control valve and bleed the system of air. Reconnect the pilot line
and leak-test all connections by brushing on a soap solution.

Figure 11 - Supply
Piping Connection

WARNING: All components of a gas supply
system must be leak tested prior to placing
equipment in service. NEVER TEST FOR
LEAKS WITH AN OPEN FLAME. Failure to
comply could result in personal injury, property
damage or death.

Manifold or Orifice Pressure Settings

Measuring manifold gas pressure cannot be done until the heater is in
operation. It is included in the steps of the "Check-Test-Start" proce-
dure in Paragraph 25. The following warnings and instructions apply.

WARNING: Manifold gas pressure must never
exceed 3.5" w.c. for natural gas and 10" w.c. for
propane gas.

For Natural Gas: When the heater leaves the factory, the combination
gas valve is set so that the manifold gas pressure is regulated to 3.5" w.c.
Inlet supply pressure to the valve for natural gas must be a minimum of
5" w.c. or as noted on the rating plate and a maximum of 14" w.c.

For Propane Gas: When the heater leaves the factory, the combination
gas valve is set so that the manifold gas pressure is regulated to 10" w.c.

Figure 10 - Vertical Vent Terminals

10. Venting (cont'd)

6’ (2M) minimum

6’ (2M) minimum

Approved clearance thimble

for single-wall vent pipe is

required when flue pipe

extends through

combustible materials.

Parapet or Adjoining Building

Vertical flue extension to

be 6” (152mm) higher than

anticipated snow depth but

no less than 2 feet (610mm)

above the roof.

Vertical pipe extension

must be insulated.

Roof Flashing

Roof - pitched

from 0 to 45°

Vertical flue extension

to be 6” (152mm) higher

than anticipated snow

depth but no less than

2 feet (610mm) above the

roof.

6” (152mm) minimum

Roof Flashing

Roof - pitched

from 0 to 45°

Approved clearance thimble is

required when flue pipe extends

through combustible materials.

Follow the requirements of the

double-wall pipe manufacturer.

Follow instructions on page 9

to join single and double-wall

pipe and to seal the connection.

Parapet or Adjoining Building

Single-Wall Vent Run and Single-Wall Terminal End

Single-Wall Vent Run and Double-Wall Terminal End

This manual is related to the following products: