beautypg.com

Optional dampers and controls (cont'd) – Reznor XE Unit Installation Manual User Manual

Page 37

background image

Form I-XE/CRGB/RPB, Page 36

Outside Air

Damper CLOSED

Return Air Damper OPEN

Rod for Outside

Air Damper

Set Screw

Outside

Air

Damper

Arm

Return

Air

Damper

Arm

Rod for Return

Air Damper

Damper

Motor

Pressure Null Switch (Used to control Outside Air
Dampers in Inlet Air Option AR23)

The pressure null switch used in Option AR23 is a Dwyer
#1640-0 with a range of .01-.20" w.c. It is shipped separately
for field installation. Refer to the following paragraphs and
the manufacturer's installation instructions included with the
switch.
Description and Application - The pressure null switch is a
diaphragm operated differential pressure switch used in
makeup air applications to control building pressure. It main-
tains a selected positive or negative pressure setpoint by
changing the amount of outside air being introduced to the
building through the modulating outside air dampers. As more
pressure is required in the building, the pressure null switch
activates the damper motor driving the outside air damper
towards the full open position and the recirculated air damper
towards the closed position. Conversely, as less pressure is
required, the switch drives the dampers in the opposite direc-
tion.

Installation Instructions for Pressure Null Switch
(See FIGURE 41D)

1. Select an indoor location free from excessive vibration

where oil or water will not drip onto the switch and where
ambient temperature will be within a range of -30°F (dry
air) to 110°F.

2. Mount the switch with the diaphragm in a vertical

plane. The switch is position sensitive and is calibrated to
operate properly when the diaphragm is vertical. Mount
switch securely.

Furnace

Section

Blower

Blower Cabinet

30% Outside Air Damper

30% Outside

Air Hood

Damper Motor

Return Air

4

1

2

3

5

6

7

8

FIGURE 41A - Control
Locations for Air Inlet/
Damper Options on Indoor
Models XE/HXE

FIGURE 41B - Location of Controls for 30% Outside Air Hood
and Damper Options (AR6 or AR7) - Outdoor Models only

FIGURE 41D - Example of

Outside Air and Return

Air Damper Linkage

Damper Linkage - When
units are equipped with
dampers, the dampers are
closed during shipment. When
there are both return air and
outside air dampers, the
return damper linkage
must be adjusted prior to
use.

7

8

1

2

3 4 5 6

9

FIGURE 41C -
Control
Locations for
100% Outside
Air and 100%
Return Air
Damper
Options on
Outdoor
Models

1 Damper Motor
2 Return Air

Damper

3 Potentiometer
4 Potentiometer
5 Mixed Air

Controller

6 Warmup Control

34. Optional Dampers and Controls (cont'd)

1 Outside Air Damper
2 Return Air Damper
3 Damper Motor
4 Potentiometer
5 Mixed Air Controller
6 Outside Air

Changeover

7 Warmup Control
8 Potentiometer

1. Loosen the set screw on the return air damper rod at the damper arm.
2. Manually open the return air dampers. While the dampers are opening, the

damper rod and arm will automatically move to their correct positions.

3. Tighten the set screw.

7 Outside Air Damper
8 Damper Motor Transformer
9 DDC Interface Control

Electric Box

Span

Adjust

Screw

Mounting Plate

Pressure Taps

Low

High

Pressure

Adjust Screw

Increasing

Decreasing

Linkage to

Diaphragm

Low

Common

High

Span Adjustment

Span of

floating

contact

Switching action in the pressure null switch

FIGURE 41D -

Pressure Null

Switch (used with

Inlet Air Option

AR23)

3. Connect the pressure taps on the top of the switch to sources of air pressure

differential. Metal tubing with 1/4" O.D. is recommended, but any tubing
system which will not unduly restrict the air flow may be used. To maintain a
positive building pressure, vent the low pressure tap to the outdoors and allow
the high pressure tap to monitor building pressure. To maintain a negative
building pressure, reverse the functions of the high and low pressure taps. In
either case, be sure that the outdoor vent is protected from the wind and
screened from insects.