Reznor XE Unit Installation Manual User Manual

Page 11

background image

Form I-XE/CRGB/RPB, Page 10

*Optional

Downturn Plenum

Furnace

Blower

Cabinet

Curb

Cap

1-7/8”

(48mm)

Roof

Curb

16” (406mm)

1-7/8”

(48mm)

AC

D

Return

Duct

Supply

Duct

1-7/8”(48mm)

1-1/2”

(38mm)

Lift Holes

(4 corners)

B

** C and D are roof opening
dimensions.

*** Field installed means that the cooling coil cabinet with or without the downturn is factory assembled
and shipped separately. The roof curb is sized to accommodate the complete length of the system. The
shipped-separate cooling coil cabinet with or without a downturn must be lifted to the roof separately
from the packaged system, set on the roof curb, and attached to the furnace section (see instructions
beginning on page 38).

16”

(406mm)

1-7/8”(48mm)

(102mm)

2 x 6 Wood Nailer

1-1/2 x 3 lb

Fiberglass

Flashed by the

installer (flashing must

be under lip of curb)

Lag Screw

Cap

Screws

For top 4 holes (2 on

each side) at both joints,

from inside the curb insert

(4) 5/16” x 1” lag screws

and (4) 5/16” lockwashers.

For bottom 4 holes (2 on each side) at both

joints, from outside of the curb insert (4)

5/16-18 x 3/4” long cap screws. Attach with

5/16” lockwashers and 5/16-18 hex nuts.

(Inside

of Curb)

7B. Mounting Outdoor Models on a Roof Curb (cont'd)

Curb Cap

Counter Flashing

(by installer)

Cant Strip

(by installer)

MUST be sealed

between curb cap

and roof curb

2 x 6

Wood

Nailer

Insulation

16”

(406 mm)

Curb Height

Cabinet

Curb Cap “Skirt”

Weld, bolt, or lag screw curb to deck structure.

Roof Curb

Roofing Felts

(by others)

IMPORTANT: Top surface of curb MUST be sealed. See instructions above.

*

Illustration is shown with an Option AQ5 or AQ8 downturn plenum. The system can have a

variety of configurations which affect installation.

• If the system does not have a downturn plenum, the discharge is horizontal.
• Downturn plenum Options AQ5 and AQ8 are factory installed to be lifted to the roof

and set on the roof curb as part of the packaged system.

• If the system has an Option AU2 or AU3 cooling coil cabinet, the discharge is horizontal. If

the system has an AU11, AU12, AU13, AU14 cooling coil cabinet, there is a downturn
plenum with vertical discharge. Options AU2, AU3, AU11, AU12, AU13, and AU14 are
not factory installed. Options AU2, AU3, AU11, AU12, AU13, and AU14 must be
lifted to the roof separately from the packaged system, set on the roof curb, and
attached to the furnace.

FIGURE 8 -
Optional Roof Curb

Splicing

Detail

Corner Detail

Curb Section

Typical
Curb
Detail

IMPORTANT: Area enclosed

by the roof curb must comply with

clearance to combustible materials.

If roof is constructed of combustible

materials, area within curb must be either ventilated, left open, or covered

with non-combustible material which has an "R" value of at least 5.0. If

area within curb is left open, higher radiated sound levels may result.

Roof Curb Dimensions (inches)

S ize

75, 100,

125

150, 175

200, 225

250, 300

350

400

S ize

75, 100,

125

150, 175

200, 225

250, 300

350

400

A

60-5/8

60-5/8

60-5/8

60-5/8

60-5/8

60-5/8

A

98-3/8

103-7/8

109-3/8 117-21/32 123-5/32 128-21/32

B

24-5/16

29-13/16

35-5/16

43-9/16

49-1/16

54-1/2

B

24-5/16

29-13/16

35-5/16

43-9/16

49-1/16

54-1/2

C**

56-15/16 56-15/16 56-15/16 56-15/16

56-15/16

56-15/16

C**

94-5/8

100-1/8

105-5/8 113-29/32 119-13/32 124-29/32

D**

20-9/16

26-1/16

31-9/16

39-13/16

45-5/16

50-13/16

D**

20-9/16

26-1/16

31-9/16

39-13/16

45-5/16

50-13/16

A

84-9/16

84-9/16

84-9/16

84-9/16

84-9/16

84-9/16

A

122-3/8

127-7/8

133-3/8 141-21/32 147-5/32 152-21/32

B

24-5/16

29-13/16

35-5/16

43-9/16

49-1/16

54-1/2

B

24-5/16

29-13/16

35-5/16

43-9/16

49-1/16

54-1/2

C**

80-13/16 80-13/16 80-13/16 80-13/16

80-13/16

80-13/16

C**

118-5/8

124-1/8

129-5/8 137-29/32 143-13/32 148-29/32

D**

20-9/16

26-1/16

31-9/16

39-13/16

45-5/16

50-13/16

D**

20-9/16

26-1/16

31-9/16

39-13/16

45-5/16

50-13/16

Option CJ4 - Roof Curb for (H)CRGB and (H)RPB with Field-

Installed*** Cooling Coil Cabinet Option AU2 or AU3

Option CJ5 - Roof Curb for (H)CRGB and (H)RPB with Field-

Installed*** Cooling Cabinet and Downturn Plenum Option AU11,

AU12, AU13, or AU14

Option CJ2 - Roof Curb for (H)CRGB and (H)RPB with Factory-

Installed Downturn Plenum Option AQ5 or AQ8

Option CJ1 - Roof Curb for (H)CRGB and (H)RPB