beautypg.com

Installation (cont.), Backwash flow control replacement, Plumbing connections – Culligan Platinum Plus Series User Manual

Page 18: Bypass valve installation

background image

14

Installation

(cont.)

Backwash Flow Control Replacement:

• Remove the drain clip and pull the drain elbow straight off.
• Remove the backwash flow control located behind the elbow.
• Install the correct backwash flow control.
• Reverse the procedure to reassemble.

Plumbing Connections

Shipped with each softener is a Culligan

®

bypass valve, which is used to connect the softener to

the plumbing system. The bypass allows the softener to be isolated from the water service line if

service is necessary while still providing water to the home. See the parts list for connectors that

are available.

Bypass Valve Installation

The bypass valve connects directly to the

control valve with a pair of couplings and

two assembly pins. Lubricate all O-rings on

the couplings with silicone lubricant.
The bypass valve is in the service position

when the handle is rotated as far back as

possible (See figures 7a and 7b).

Caution! Close the inlet supply line and relieve system pressure before cutting into

the plumbing! Flooding could result if not done!
Caution! When making sweat connections, use care to keep heat away from the

plastic nuts used to connect the plumbing to the bypass. Damage to these components

may otherwise result.

Note: If the ground from the electrical

panel or breaker box to the water meter

or underground copper pipe is tied to

the copper water lines and these lines

are cut during installation of the bypass

valve, an approved grounding strap must

be used between the two lines that have

been cut in order to maintain continuity. The length of the grounding strap will depend upon

the number of units being installed. In all cases where metal pipe was originally used and is

later interrupted by the bypass valve to maintain proper metallic pipe bonding, an approved

ground clamp c/w not less than #6 copper conductor must be used for continuity. Check your

local electrical code for the correct clamp and cable size.

Caution! To bypass the valve, turn bypass knob on both sides of the valve to bypass

position (see figure 7b). When returning to service, put the inlet into service before the

outlet.

Note: The number on the flow control should face into the valve body.
Note: Dip switch #5 is to be in the “off ” position for 10” and 12” Tanks (0.25 gpm

refill flow control). Dip switch 5 is to be in the “on” position for 14” and 16” tanks (0.50

gpm brine refill flow control).

Figure 7a

Figure 7b