beautypg.com

7can connection – EVCO c-pro micro User Manual

Page 36

background image

C-PRO MICRO HARDWARE MANUAL

Page 36

7

CAN Connection

C-PRO MICRO can be connected to other controllers, to expansion modules and to one or more user interfaces
using either local or wide CAN serial port. The CAN bus uses the ISO 11898 standard, a balanced two-wire
communication very similar to the RS 485 standard.
Resistors with a recommended rating of 120-124 ohm have to be fitted at each end of the bus.




























If connection is established through the Local CAN bus, it is possible to power a user interface using the 4-
terminal connector, according to the following table:

C-PRO MICRO

V-VIEW User Interface

PA 1 (VCD) needs independent power supply

C3-1 (CAN+)

PA 2 (CAN+)

C3-3 (CAN-)

PA 3 (CAN-)

C3-2 (GND )

PA 4 (GND )

The maximum number of expansions and user terminals is 32.

The maximum number of controllers for the user terminal V-VIEW is 2.

CAN

NODE

(C-PRO

MICRO)

CAN

NODE

(V-VIEW)

CAN

NODE

(C-PRO EXP

MICRO)

120ohm

120ohm

CAN+

CAN-