beautypg.com

6 electrical characteristics – EVCO c-pro micro User Manual

Page 14

background image

C-PRO MICRO HARDWARE MANUAL

Page 14

3.6

Electrical characteristics


CPU

Microcontroller

8 bit

Program flash memory

128 Kbyte

RAM for data memory

4 Kbyte

EEPROM

4 Kbyte

A/D

8 channels at 10 bit

Power supply

Voltage

12 V AC/DC

Range

-10% +15%

Frequency

50/60 Hz / DC

Maximum input power

6 VA

Fuse rating

External

Digital outputs

Number

6

Type

Electromechanical relays

Maximum breaker current at 250 V AC
Please note:
maximum current for common contact
(DO4+DO5): < 4 A

maximum current for the other
contacts: < 3 A

3(1) A

Number of processing cycles

100.000

Minimum switching interval

20 s

Micro-switch action type

1C

Insulation between relays and low
voltage

Reinforced

Insulation between relays

Functional

Insulation between relays and DO6

Reinforced

Digital inputs

Number

5

Type

Clean contact

Breaker closure current to earth

2 mA

Maximum closure resistance

100 Ω

OFF to ON detection time

100 ms

ON to OFF detection time

100 ms

Analogue inputs for

Number

2

NTC probes

Type

NTC (10 KΩ ±1% @25

°

C)

NTC measurement range

-40

°

C

÷

100

°

C

NTC measurement accuracy

±1

°

C

NTC measurement sensitivity

0.1

°

C

Analogue inputs for

Number

2

NTC probes or
ratiometric pressure

Type

NTC (10 KΩ ±1% @25

°

C)

transducers

NTC measurement range

-40

°

C

÷

100

°

C

NTC measurement accuracy

±1

°

C

NTC measurement sensitivity

0.1

°

C

Type

Current

Current measurement range

0/4

÷

20 mA

Current measurement accuracy

±0.08 mA

Current measurement sensitivity

0.01 mA

Input resistance

200 Ohm