6 electrical characteristics – EVCO c-pro micro User Manual
Page 14
C-PRO MICRO HARDWARE MANUAL
Page 14
3.6
Electrical characteristics
CPU
Microcontroller
8 bit
Program flash memory
128 Kbyte
RAM for data memory
4 Kbyte
EEPROM
4 Kbyte
A/D
8 channels at 10 bit
Power supply
Voltage
12 V AC/DC
Range
-10% +15%
Frequency
50/60 Hz / DC
Maximum input power
6 VA
Fuse rating
External
Digital outputs
Number
6
Type
Electromechanical relays
Maximum breaker current at 250 V AC
Please note:
maximum current for common contact
(DO4+DO5): < 4 A
maximum current for the other
contacts: < 3 A
3(1) A
Number of processing cycles
100.000
Minimum switching interval
20 s
Micro-switch action type
1C
Insulation between relays and low
voltage
Reinforced
Insulation between relays
Functional
Insulation between relays and DO6
Reinforced
Digital inputs
Number
5
Type
Clean contact
Breaker closure current to earth
2 mA
Maximum closure resistance
100 Ω
OFF to ON detection time
100 ms
ON to OFF detection time
100 ms
Analogue inputs for
Number
2
NTC probes
Type
NTC (10 KΩ ±1% @25
°
C)
NTC measurement range
-40
°
C
÷
100
°
C
NTC measurement accuracy
±1
°
C
NTC measurement sensitivity
0.1
°
C
Analogue inputs for
Number
2
NTC probes or
ratiometric pressure
Type
NTC (10 KΩ ±1% @25
°
C)
transducers
NTC measurement range
-40
°
C
÷
100
°
C
NTC measurement accuracy
±1
°
C
NTC measurement sensitivity
0.1
°
C
Type
Current
Current measurement range
0/4
÷
20 mA
Current measurement accuracy
±0.08 mA
Current measurement sensitivity
0.01 mA
Input resistance
200 Ohm