beautypg.com

EVCO c-pro micro User Manual

Page 10

background image

C-PRO MICRO HARDWARE MANUAL

Page 10

Connector 2:

Connection for the parameter upload/download key and/or output for RS485 module

and/or controller flash download module

Connector 3:

Analogue output connector (optional, not available for open versions)

Conn.

Abbrev.

Description (V+I version)

C3-1

AO2

0-10 V DC

C3-2

GND

Common analogue output

C3-3

AO3

4-20 mA

Description (I+I version)

C3-1

AO2

4-20 mA

C3-2

GND

Common analogue output

C3-3

AO3

4-20 mA

Description (V+V version)

C3-1

AO2

0-10 V DC

C3-2

GND

Common analogue output

C3-3

AO3

0-10 V DC

Connector 4:

Connector for low voltage signals

Conn.

Abbrev.

Description

C4-1

12 V AC (Power)

Device power supply (12 V AC/DC)

C4-2

5V

Ratiometric power supply

C4-3

GND

Common analogue and digital inputs

C4-4

GND

Common analogue and digital inputs

C4-5

AI4

Analogue input No. 4 (for NTC probes or for 0/4-20 mA or 0-5V
transducers)

C4-6

AI3

Analogue input No. 3 (for NTC probes or for 0/4-20 mA or 0-5V
transducers)

C4-7

AI2

Analogue input No. 2 (for NTC probes)

C4-8

AI1

Analogue input No. 1 (for NTC probes)

C4-9

12 V AC (Power)

Device power supply (12 V AC/DC)

C4-10 12 V DC

Current transducer and cut-off module power supply (50 mA max.
not protected against short circuits)

C4-11 AO1

Cut-off module impulse output

C4-12 DI5

Digital input No. 5

C4-13 DI4

Digital input No. 4

C4-14 DI3

Digital input No. 3

C4-15 DI2

Digital input No. 2

C4-16 DI1

Digital input No. 1

Connector 5:

Connector for remote keypad and I/O expansion unit (IntraBus)

Conn.

Abbrev.

Description

C5-1

VDC

Remote keypad power supply (12 V DC 50 mA max.; not protected
against short circuits)
(Please note: any expansion units must have a local power supply)

C5-2

GND

Common

C5-3

DATA

Powered serial connection