EVCO c-pro mega User Manual
Page 42

C-PRO MEGA HARDWARE MANUAL
Page 42
8 Configuration of the supplied analogic outputs signal
C-PRO MEGA has four analogic outputs.
Each analogic output can be configured to supply one of the following signal :
•
0,5-10 V (called “voltage”)
•
0-20 mA (called “current”)
•
4-20 mA (called “current”).
To configurate the signal supplied by the analogic output it is necessary :
•
positioning the appropriate JMP6 jumper in the selected position (see chapter “C-PRO
MEGA wiring layout, jumper and LED meaning ; the configuration jumper is JMP6)
•
confirming the choice selected with the “controller parameters” relative to the analogic
outputs as shown on the following paragraph .
8.1.1 Parameters configuration relative to the analog output
By logging on the controller parameters’ configuration procedure relative to the analogic outputs act in the
following way :
Both for the remote or built-in user interface :
1.
Ensure that the controller and the user interface are both switched on and any utilization be connected
with the analogic outputs
2.
Keep both
and
buttons pressed together for two seconds : firsts voice available
will be visualized.
3.
Press and release
button to select “Parameters”.
4.
Press and release
button : “Input Password” will be visualized.
5.
Press and release
button: the cursor blinks.
6.
Press and release
button to set “ -19”.
7.
Press and release
button: firsts available voice will be visualized.
8.
Press and release
button: further available voice will be visualized.
9.
Press and release
button to select one of the voice “Type AO1 … AO4”.
10.
Press and release
button: the cursor blinks.