Jumpers and LEDs meanings
The controller also has some configuration jumpers:
JMP1
Selection of analogic AI1 input
Jumper not inserted
0-10V input
Jumper inserted
0-5V, 0-20mA, 4-20mA, NTC, PTC input
JMP2
Selection of analogic AI2 input
Jumper not inserted
0..10V input
Jumper inserted
0-5V, 0-20mA, 4-20mA, NTC, PTC input
JMP3
CAN termination
Jumper not inserted
(120
Ω
) termination not inserted
Jumper inserted
(120
Ω
) termination inserted
JMP4
Local CAN Baud Rate selection
A
B
Jumper A inserted
Jumper B inserted
Baud rate = 20K
A
B
Jumper A inserted
Jumper B not inserted
Baud rate = 50K
A
B
Jumper A not inserted
Jumper B inserted
Baud rate = 125K
A
B
Jumper A not inserted
Jumper B not inserted
Baud rate = 500K
JMP5
RS-485 termination
Jumper not inserted
(120
Ω
) termination not inserted
Jumper inserted
(120
Ω
) termination inserted
JMP6
Selection of Analogic Outputs
A
B
C
D
Jumper A inserted
Jumper B inserted
Jumper C inserted
Jumper D inserted
AO1 Output as current
AO2 Output as current
AO3 Output as current
AO4 Output as current
A
B
C
D
Jumper A not inserted
Jumper B not inserted
Jumper C not inserted
Jumper D not inserted
AO1 Output as voltage
AO2 Output as voltage
AO3 Output as voltage
AO4 Output as voltage
Besides the jumpers setting, for the analogic output signals supplied configuration, the settlement of the
controller parameters is also necessary ( see the chapter 8 : output signals supplied configuration)