2 general features – EVCO c-pro mega User Manual
Page 24
![background image](/manuals/675453/24/background.png)
C-PRO MEGA HARDWARE MANUAL
Page 24
3.2
General features
C-PRO
MEGA
open
C-PRO
MEGA
sealed (1)
C-PRO
MEGA
sealed (2)
C-PRO
MEGA
built-in
Microprocessor
16 bit
16 bit
16 bit
16 bit
Oscillator frequency 16 MHz
16 MHz
16 MHz
16 MHz
Flash program
memory
256K
128K
256K
256K
RAM data storage
memory
8K
6K
8K
8K
CPU
A/D converter
8 channels
10bit
8 channels
10bit
8 channels
10bit
8 channels
10bit
Number
0
1
0
0
type
CAN V2.0B
Optoisolated
Physical layer
2 wires +
common wire
(ISO 11898)
Baud rate (max.
length = 1000 m)
20K
Baud rate (max.
length = 400 m)
50K
Baud rate (max.
length = 250 m)
125K
Baud rate (max.
length = 50 m)
500K
Connector
Disconnectable
screw
terminals
WideCAN
communication bus
(optional)
Note: baud rate can be selected by parameter
Note: The physical level of the CAN consists of a cable with twisted pair (both shielded and
not shielded). The terminator's impedance is 120
Ω
.
Number
0
1
1
0
type
RS485,
optoinsulated
RS485,
optoinsulated
Physical layer
2 wires +
common
2 wires +
common
Baud rate (max.
length 1000 m)
1200 - 19200
1200 - 19200
Connector
Disconnectable
screw
terminals
Disconnectable
screw
terminals
RS485 serial
communication
(UART2)
(optional,
alternative to
RS232)
Note: baud rate can be selected by parameter
Note: The physical level of the CAN consists of a cable with twisted pair (both shielded and
not shielded). The terminator's impedance is 120
Ω
.
Number
0
1
1
0
type
RS232
optoinsulated
RS232
optoinsulated
Physical layer
Tx,Rx +
2 signal for
modem control
+ common
Tx,Rx +
2 signal for
modem control
+ common
Baud rate (max.
length 1000 m)
1200 - 19200
1200 - 19200
RS232 serial
communication
(UART2)
(optional,alternative
to RS232)
Connector
Sub-D 9 pin
male
Sub-D 9 pin
male
128 KB instead of 256 KB program memory built-in with WideCAN serial output version of the controller is
available on request.