beautypg.com

EVCO c-pro mega User Manual

Page 27

background image

C-PRO MEGA HARDWARE MANUAL

Page 27

Note:

1)

baud rate selectable by two jumpers

2)

The CAN connection consists of a cable with twisted pair (both
shielded and not shielded). The first and the last elements of the
system must have the bus terminating resistor connected (impedance
is 120

). A second twisted pair is used for the feed and the ground

Number

1

type

RS485, optoinsulated

Physical layer

2 wires + common wire

Baud rate (max. length 1000 m)

1200 - 19200

Connector

Disconnectable screw
terminals

type

RS232, optoinsulated

Physical layer

Tx, Rx + 2 signals for
modem control + common
wire

Baud rate (max. length 3 m)

1200 - 19200

Connector

Disconnectable screw
terminals






RS485 serial
communication
(UART1)

Note:

1)

baud rate is selectable by parameters

2)

The CAN connection consists of a cable with twisted pair (both

shielded and not shielded). The first and the last elements of the
system must have the bus terminating resistor connected (impedance
is 120

). A second twisted pair is used for the feed and the ground

Number

1

Backup type

Supercap


RTC
(Real Time Clock)

RTC data retention time in the event of a
power failure

3 days

Buzzer

Number

1

Signaling LEDs

Number

6


The open case version of the controller is available with the fixed screw terminals only.