In the previous page, example of connection of C-PRO AL with C-PRO MEGA.
With the same secondary of the transformer, is possible to feed both C-PRO AL and the C-PRO MEGA low
voltage digital input (they work with 12-24 VAC/DC).
It is preferable :

To connect the possible remote user interface to Local CAN (not optoinsulated)

port (providing the remote user interface with the necessary 12 Vdc power supply)

To connect the possible expansion to the Wide CAN (optoinsulated) port.


The controller and C-PRO EXP Mega power supplies have to be electrically insulated one from the

other.