Comtrol ES8508 Series User Guide User Manual
Page 205
RocketLinx ES8508 Series User Guide: 2000575 Rev. A
Modbus TCP Register Table - 205
ModBus TCP /IP Support
0x020A
2 words
Firmware Release Date
Firmware was released on 2010-08-11 at 09
o’clock
Word 0 = 0x0B09
Word 1 = 0x0A08
0x020C
3 words
Ethernet MAC Address
For example: MAC = 01-02-03-04-05-06
Word 0 Hi byte = 0x01
Word 0 Lo byte = 0x02
Word 1 Hi byte = 0x03
Word 1 Lo byte = 0x04
Word 2 Hi byte = 0x05
Word 2 Lo byte = 0x06
0x0300
2 words
IP address
For example: IP = 192.168.250.250
Word 0 Hi byte = 0xC0
Word 0 Lo byte = 0xA8
Word 1 Hi byte = 0x0A Word 1 Lo byte = 0x01
0x020F to 0x2FF
241 words
Reserved address space
0x0302
2 words
Subnet Mask
0x0304
2 words
Default Gateway
0x0306
2 words
DNS Server
0x0308 to 0x3FF
248 words
Reserved address space (IPv6 or others)
0x0400
1 word
AC1
0x0000:Off
0x0001:On
0xFFFF: unavailable
0x0401
1 word
AC2
0x0000:Off
0x0001:On
0xFFFF: unavailable
0x0402
1 word
DC1
0x0000:Off
0x0001:On
0xFFFF: unavailable
0x0403
1 word
DC2
0x0000:Off
0x0001:On
0xFFFF: unavailable
0x0404 to 0x040F
12 words
Reserved address space
Word Address
Data Type
Description