beautypg.com

Coil – Carrier 42V User Manual

Page 46

background image

46

BALL VALVE

GATE

SHUT OFF

(1) GATE
(1) BALL
(1) 2-WAY MOTORIZED

R

S

COIL

BALL VALVE

BALL VALVE

(2) BALL
(1) BALANCING
(1) 2-WAY MOTORIZED

R

S

COIL

CIRCUIT SETTER

BALL VALVE

(1) BALL
(1) CIRCUIT SETTER
(1) 2-WAY MOTORIZED

R

S

COIL

MOTORIZED

2-WAY VALVE

A

BYPASS

BALANCING
VALVE

A

MOTORIZED

2-WAY VALVE

BYPASS

A

MOTORIZED

2-WAY VALVE

BYPASS

M

M

M

Fig. 44 — Two-Way Motorized Control Valve Package

Fig. 45 — Two-Way Motorized Control Valve Package with Aquastat Bleed Bypass Line

The 2-way motorized valve motor drives valve open and a
spring returns valve to normally closed position (no water
flow with unit OFF).
Supply connection at coil will be swage fit for field braze
(standard) or union (option). Return connection at coil will
be factory brazed if isolation valve only. Addition of any
other component will require swage fit for field braze or
optional union connection.
Check job specifications for system pressure, pressure drop
limitations and flow rate prior to selecting valve package
components or valve package size (

1

/

2

in.,

3

/

4

in., etc.).

2-PIPE SYSTEM (One Valve Package) or 4-PIPE SYSTEM
(Two Valve Packages) Application:
• 2 Pipe — Hydronic Heating Only
• 2 Pipe — Hydronic Cooling Only
• 2 Pipe — Hydronic Cooling with Total Electric Heat
• 4 Pipe — Hydronic Cooling and Heating
NOTE: A

1

/

4

-in. bypass line is included in the piping pack-

age when a 2-way valve is specified with a control package
containing an automatic changeover device.

The 2-way motorized valve motor drives valve open and a
spring returns valve to normally closed position (no water
flow through coil with unit OFF).
The aquastat bleed bypass bleeds a small amount of water
from supply to return when control valve is closed (required
for system water temperature sensing by aquastat).
Aquastat (A) clips on supply line upstream from aquastat
bleed bypass (as shown at right). It senses system water
temperature to prevent cooling operation with hot water in
system piping or heating operation with chilled water in
system piping. Additional aquastat required to lock out the
optional auxiliary electric heat when hot water in system.
Supply and return connections at coil will be swage fit for
field braze (standard) or unions (option).
Check job specifications for system pressure, pressure drop
limitations and flow rate prior to selecting valve package
components or valve package size (

1

/

2

in.,

3

/

4

in., etc.).

2-PIPE SYSTEM (One Valve Package) Application:
• 2 Pipe — Hydronic Cooling and Heating
• 2 Pipe — Hydronic Cooling and Heating with Auxiliary

Electric Heat

NOTES: Additional aquastat required as noted above.

LEGEND

Ball Valve

Motorized 2-Way Valve

LEGEND

Balancing Valve

Ball Valve

Circuit Setter

Gate Shut Off Valve

Motorized 2-Way Valve

M

MOTORIZED

MOTORIZED

a42-4174

MOTORIZED

MOTORIZED

M

a42-4175