beautypg.com

Figure 3.9, Combustion safeguard status indicator led location, Figure 3.10 – AERCO KC1000 Heater w/Mod-Box Controller User Manual

Page 19: Water level test and reset switch locations, Control panel operating procedures

background image

CONTROL PANEL OPERATING PROCEDURES

14

3.6 THE COMBUSTION SAFEGUARD
CONTROLLER

The Combustion Safeguard is responsible for
monitoring the safety components during the start
sequence, and after flame is established. It is also
responsible for timing of the purge and ignition
cycles during the start sequence.

The combustion safeguard is located on the left
side of the control panel as shown in Figure 3.9.
There are five status LEDs that indicate the
status of operation. Along with the annunciator,
these are useful as a double check for proper
system operation and troubleshooting. The table
below defines the function of each light. The
reset button located under the LEDs is to reset
the combustion safeguard on lockout.

DESCRIPTION

FUNCTION

POWER

Lights upon power up of

the unit.

PILOT

Lights when there is a call

for heat.

FLAME

Lights once flame has

been detected.

MAIN

Lights after flame has

been detected and

stabilized

ALARM

This lights when the

controller is in a LOCKOUT

condition.

Figure 3.9

Combustion Safeguard Status Indicator LED

Location

3.7 WATER LEVEL TEST and RESET
SWITCHES

The water level switches are located on the left
side of the panel (see Fig. 3.10). When depressed
the TEST switch simulates a low water level
condition by breaking the connection between the
water level probe and the sensing circuitry. To test
the water level circuitry, depress the test switch for
3 seconds. The unit should fault resulting in the
red fault light blinking and the LED display
indicating LOW WATER LEVEL.

Figure 3.10

Water Level Test and Reset Switch Locations

Note:

Only water level circuitry is tested during the

above test. To determine if the probe is

functioning properly, the water level must be

reduced below the level of the probe.

To reset the unit, depress the water level reset
switch, the annunciator clear button, and if
necessary, the reset button on the combustion
safeguard.

3.8 ON/OFF SWITCH

The ON/OFF switch is located on the right side of
the control box above the temperature controller
(see Figure 3.1). It is part of the start string and
must be in the ON position to enable the unit to
fire. When the switch is in the ON position and
illuminated, it is indicating that the start limit
string, consisting of water temperature, gas
pressure, water level, and the interlock is
satisfied. The unit, at this point, is in standby
mode and ready to run.