Post-installation setup and calibration, Control system menu changes for low nox operation, Post-purge timeout for c-more control system – AERCO KC Standard to Low NOx Convertion Instructions User Manual
Page 31

31
5. POST-INSTALLATION SETUP AND CALIBRATION
Following installation of all Low NOx Conversion Kit items, it will be necessary to adjust several
operating parameters using the unit’s Control System menus. In addition, combustion calibration
procedures MUST be performed to ensure Low NOx compliance, prior to placing the unit into service.
The procedures in this section are divided into the following main categories:
• Low NOx Operating Parameter Menu Changes
• Combustion Calibration Setup
• Combustion Calibration Procedures for Units With C-More or Modular Control Systems
• Combustion Calibration Procedures for Units With Digital (CCC) Control Systems
• Unit
Reassembly
These procedures are provided in paragraphs 5.1 through 5.5 respectively. For more detailed
information on the operation of your KC1000 unit, refer to the applicable Operation & Maintenance
Manual for the installed Control System as follows:
Unit
C-More Control
System
Modular Control
System
Digital (CCC) Control
System
KC1000 Boiler
GF-109LN
GF-106
GF-102
KC1000 Heater
GF-111LN
GF-105
GF-101
NOTE
If the KC1000 is equipped with an older style Digital (CCC) Control System,
no menu changes are required.
5.1 Control System Menu Changes for Low NOx Operation
If the KC1000 is equipped with either a C-More or Modular Control System, several menu changes
may need to be made to ensure Low NOx compliance. These changes will depend on which type of
control system is installed and whether the unit is a boiler or water heater.
5.1.1 Post-Purge Timeout For C-More Control System
If the unit is equipped with a C-More Control System, adjust the Post-Purge Timer in the Factory
Menu to 10 seconds as follows:
1.
Apply external AC power to the unit.
2.
Set the Control Box ON/OFF switch to OFF.
3.
Access the Password entry in the Setup menu.
4.
Enter and store the Factory Password (2807). Password 3 will be displayed indicating that the
valid Factory password has been entered.
5.
Next, scroll through the Factory Menu until Post Purge Timer is displayed.
6.
Set the Post Purge Timer menu option to 10 sec. and store the entry.