Section 6 - safety device testing procedures, 1 testing of safety devices, 2 low gas pressure test – AERCO KC1000 Boiler equipped with C-More version 3.04 User Manual
Page 45: 3 high gas pressure test

SAFETY DEVICE TESTING
SECTION 6-SAFETY DEVICE TESTING PROCEDURES
6.1 TESTING OF SAFETY DEVICES
Periodic testing of all controls and safety devices 
is required to insure that they are operating as 
designed. Precautions must be taken while tests 
are being performed to protect against bodily 
injury and property damage. 
 
Systematic and thorough testing of the operating 
and safety controls should be performed on a 
scheduled basis, or whenever a control compo-
nent has been serviced or replaced. All testing 
must conform to local jurisdictions or codes such 
as ASME CSD-1. 
 
NOTE:
MANUAL and AUTO modes are required to
perform the following tests. For a complete
explanation of these modes, see Section 3.
NOTE:
It will be necessary to remove the sheet 
metal covers and cap from the unit to 
perform the following tests. 
WARNING!
ELECTRICAL VOLTAGES IN THIS 
SYSTEM INCLUDE 120 AND 24 VOLTS 
AC. POWER MUST BE REMOVED PRIOR 
TO PERFORMING WIRE REMOVAL OR 
OTHER TESTING PROCEDURES THAT 
CAN RESULT IN ELECTRICAL SHOCK. 
6.2 LOW GAS PRESSURE FAULT TEST
1. Shut off the gas supply to the unit. 
 
2. Install a 0-16” W.C. manometer in the gas 
pipe assembly below the low gas pressure 
switch. (See Fig. 6.1) 
 
3. Open the gas supply to the unit and depress 
the CLEAR button to clear any fault 
messages.. 
 
4. Place the unit in Manual Mode and fire the 
unit at a valve position between 25% and 
30%. 
 
5. Slowly close the manual gas supply valve 
while monitoring the gas pressure. The unit 
should fault and shutdown on LOW GAS 
PRESSURE when the manometer indicates 
approximately 6.5” W.C. 
6. Open the gas supply to the unit and press
the CLEAR button on the Control Box.
 
7. The unit should restart. 
 
Figure 6.1
1/8” Pipe Plug Position for Manometer
Installation
NOTE:
After faulting the unit, the fault message will
be displayed and the fault indicator light will
flash until the CLEAR button is pressed.
6.3 HIGH GAS PRESSURE TEST
1. Start the unit in manual mode and fire
between 25% and 30%.
 
2. Remove either wire # 150 or wire #151 from 
the high gas pressure switch. See Fig. 6.2.
 
3. The unit should shut down on a HIGH GAS 
PRESSURE FAULT.
 
4. Reconnect the wire previously removed from 
the high gas pressure switch and depress 
the CLEAR button. 
 
5. The unit should restart. 
 
 
6-1
