3 pressure relief and drain valve installation, 4 temperature/pressure indicator, Installation – AERCO KC1000 Boiler equipped with C-More version 3.04 User Manual
Page 13

INSTALLATION
Every boiler plant must have a source of make-
up water to it. As with any closed loop hydronic 
system, air elimination and expansion equip-
ment must be provided as part of the overall 
installation. All piping MUST include ample 
provision for expansion. 
 
Figure 2.3
Supply and Return Location
NOTE:
The maximum working pressure for 
installations within the Province of Alberta is 
87 psig. Therefore a pressure relief valve 
with a setting of 75 psig (or lower) should be 
installed for these installations. See Drawing 
AP-A-863 in Appendix F. 
2.3.3 PRESSURE RELIEF AND DRAIN 
VALVE INSTALLATION
An ASME rated Relief Valve is supplied with 
each unit. The supplied pressure relief valve 
setpoint will be 30, 50, 75, 100, or 150
psig as
ordered from the factory. Install the pressure 
relief valve in the tapping provided opposite the 
system supply connection, (see Figure 2.4). The
pressure relief valve should be piped in the
vertical position
using the fittings supplied. A
suitable pipe compound should be used on the 
threaded connections, and excess should be 
wiped off to avoid getting any into the valve 
body. The discharge from the relief valve should 
be piped to within 12 inches of the floor to 
prevent injury in the event of a discharge. 
The relief piping must be full size without 
reduction. No valves, restrictions, or other 
blockages should be allowed in the discharge 
line. In multiple unit installations the relief valve 
discharge lines must not be manifolded, 
(connected), together. Each must be individually 
run to a suitable discharge location. The drain 
valve provided should be installed on the right 
hand side of the unit towards the bottom of the 
shell. The valve should be pointed in the down 
position, (see Figure 2.4). 
 
 
 
Figure 2.4
Relief and Drain Valve Location
 
 
2.3.4 TEMPERATURE/PRESSURE 
INDICATOR 
The unit is supplied with one of two styles of 
Temperature/Pressure Indicators that must be 
installed in the tapping on the supply flange of 
the unit (see Figures. 2.5a and 2.5b). A suitable 
pipe compound should be used sparingly to the 
threaded connection. 
 
 
2-3
