Initial start-up – AERCO KC1000 Boiler equipped with C-More version 3.04 User Manual
Page 35

INITIAL START-UP
NOTE:
4-3
On initial start-up, or return to service from a 
fault condition, the unit will remain at a 29% 
valve position for two-minutes, although the 
control signal may indicate a greater input. 
9. Following the warm-up period, increase the
valve position in 20% increments while 
monitoring the gas pressure after each 
increase. If gas pressure dips below 8.5” 
W.C. for FM gas trains and 8.9” for IRI gas 
trains at any valve position percentage, stop 
and raise the pressure. Once 100% is 
reached, adjust the gas pressure for 8.5” 
W.C. or 8.9” W.C. 
NOTE:
If 8.5” W.C. for FM gas trains or 8.9” W.C. for IRI 
gas trains cannot be obtained at the 100% valve 
position, it will be necessary to stop calibration 
and contact the local AERCO representative in 
your area. Running the unit on insufficient gas 
pressure will void the warranty 
10. Once 8.5” W.C. or 8.9” W.C. is set at the
100% valve position, change the valve 
position to 30% and insert the combustion 
analyzer probe into the stack. 
NOTE:
Always go to a percentage of valve position from 
the same direction, (i.e., 100% to 30% or 30% to 
20%). Whenever going to a valve position from 
below (i.e., 20% to 30%), first go above then 
back down to the desired valve position. This is 
necessary due to hysteresis in the air/fuel valve 
stepper motor. Hysteresis causes the air/fuel 
valve to stop in a slightly different position if the 
valve position percentage is approached from 
below or above. This results in a difference in 
oxygen readings for the same valve position 
percentage causing unnecessary recalibration
.
11.
Allow enough time for the combustion 
analyzer to settle. Compare the measured 
oxygen level to the oxygen range for the 
existing intake air temperature in Table 1. 
 
12. If the measured oxygen level is within the 
range listed in Table 1, no adjustment is 
necessary. Proceed to step 19. 
13. If the measured oxygen level is not within
the range listed in Table 1, remove the 
regulator cap and cap gasket from the 
differential pressure regulator (see 
Figure 4.3) and proceed to step 14. 
Table 1
Combustion Oxygen Levels for a 30%
Valve Position
Inlet Air
Temp
Oxygen
(+0.2/-1.0)
Carbon
Monoxide
-20°F
7.5 %
<50 ppm
0°F
7.3 %
<50 ppm
10°F
7.2 %
<50 ppm
30°F
6.8 %
<50 ppm
50°F
6.4 %
<50 ppm
60°F
6.2 %
<50 ppm
70°F
6.0 %
<50 ppm
80°F
5.8 %
<50 ppm
90°F
5.6 %
<50 ppm
100°F
5.4 %
<50 ppm
Figure 4.3
Differential Regulator
14. Use a flat-tip screwdriver to adjust the
differential pressure regulator. Turn the 
screwdriver: 
• counterclockwise to increase the
oxygen level
• clockwise to decrease the oxygen level
15. Replace the regulator cap and cap gasket
and wait for the analyzer reading to settle.
16. When the analyzer reading settles, compare
the new oxygen reading to Table 1.
17. If necessary, repeat the adjustment until the
oxygen level is within the range specified in 
Table 1. 
 
18. Replace the regulator cap and cap gasket. 
NOTE:
Adjust only the differential regulator at 30% 
control signal; Do Not adjust the air shutter. 
 
 
 
