Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 7 – MAINTENANCE

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 97 of 210

GF-133

Ph.: 800-526-0288

03/20/14

Figure 7-3: Pilot Regulator Mounting Location

7.5.2 Pilot Regulator Pressure Calibration

If the Pilot Regulator pressure is above 5.0”W.C. or below 4.0” W.C., the Pilot Regulator
pressure must be calibrated using the following procedure:

Pilot Regulator Pressure Calibration Procedure

1. Ensure that gas supply shut-off valve upstream of the unit is still turned OFF.

2. Turn OFF electrical power to the system.

3. Remove the pipe plug from the 1/4” NPT port on the outlet side of the Pilot Regulator

(Figure 7-3) and insert a NPT-to-barbed adapter fitting.

4. Attach one end of the plastic tubing to the barbed fitting and the other end to the 16” W.C.

manometer.

5. Remove the cap from the Pilot pressure regulator and rotate the regulator adjustment

(beneath cap) clockwise (CW) to its highest possible pressure setting.

6. OPEN the main gas supply upstream of the unit.

7. Turn ON electrical power to the system.

8. Start the boiler in the MANUAL Mode. Observe the manometer pressure when the Pilot

solenoid “clicks” open after purge. The manometer should now provide a reading of 4.9”
W.C.

TO AIR/FUEL

VALVE

GAS INLET

DOWNSTREAM

LOW GAS PRESSURE

SWITCH (6.9” W.C.)

HIGH GAS

PRESSURE SWITCH

(10.5” W.C.)

MANUAL
SHUT-OFF
VALVE

UPSTREAM LOW
GAS PRESSURE
SWITCH

LEAK DETECTION PORT WITH BALL VALVE & 1/4" NPT PLUG

TEE WITH
1/4" NPT PLUG
(Install manometer
here for Pilot
Regulator
tests)

PILOT

REGULATOR

PILOT

SOLENOID

VALVE