beautypg.com

4 remote setpoint modes, 1 remote setpoint field wiring – AERCO BMK 6000 User Manual

Page 71

background image

Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 5 – MODE OF OPERATION

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 71 of 210

GF-133

Ph.: 800-526-0288

03/20/14

5.4 REMOTE SETPOINT MODES

The unit’s setpoint can be remotely controlled by an Energy Management System (EMS) or
Building Automation System (BAS). The Remote Setpoint can be driven by a current or voltage
signal within the following ranges:

• 4-20 mA/1-5 Vdc
• 0-20 mA/0-5 Vdc

The factory default setting for the Remote Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this setting,
a 4 to 20 mA/1 to 5 Vdc signal, sent by an EMS or BAS, is used to change the unit's setpoint.
The 4 mA/1V signal is equal to a 40°F setpoint while a 20 mA /5V signal is equal to a 240°F
setpoint. When a 0 to 20 mA/0 to 5 Vdc signal is used, 0 mA is equal to a 40°F setpoint.

In addition to the current and voltage signals described above, the Remote Setpoint mode can
also driven by a RS-485 Modbus Network signal from an EMS or BAS.

The Remote Setpoint modes of operation can be used to drive single as well as multiple units.

NOTE

If a voltage, rather than current signal is used to control the remote
setpoint, a DIP switch adjustment must be made on the PMC
Board located in the Control Panel Assembly. Refer to GF-112,
Appendix D for DIP switch settings, or contact your local AERCO
representative for details.

In order to enable the Remote Setpoint Mode, the following menu setting must be made in the
Configuration Menu:

Menu Option

Setting

Boiler Mode

Remote Setpoint

Remote Signal

4-20mA/1-5V, 0-20mA/0-5V,
or Network

Refer to section 3.3 for detailed instructions on changing menu options.

If the Network setting is selected for RS-485 Modbus operation, a valid Comm Address must be
entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional
information.

While it is possible to change the settings of temperature related functions, the unit is factory
preset with settings that work well in most applications. It is suggested that an AERCO
representative be contacted, prior to changing any temperature related function settings. For
descriptions of temperature-related functions and their factory defaults, refer to Appendices A
and E.

5.4.1 Remote Setpoint Field Wiring

The only wiring connections necessary for the Remote Setpoint mode are connection of the
remote signal leads from the source to the unit’s I/O Box. The I/O Box is located on the front
panel of the boiler. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are
made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are
made at the RS485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded)
at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity