beautypg.com

AERCO BMK 6000 User Manual

Page 66

background image

Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

Page 66 of 210

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0086_0D

03/20/14

Ph.: 800-526-0288

GF-133

Natural Gas Combustion Calibration (Cont.)

28. Repeat steps 20 through 27 for valve positions of 50%, 40%, 30% and 18%* (see *NOTE

below). The oxygen (O

2

), nitrogen oxide (NOx) and carbon monoxide (CO) should remain

within the same limits for all valve positions as shown in the following table.

*NOTE

Set the Valve Position at 18% but make adjustments to the
Combustion Calibration value designated as 16%.

NOTE

If NOx readings exceed the target values shown (<20 ppm),
increase the O

2

level up to 1% higher than the listed calibration

range shown in the table. Record the increased O

2

value on the

Combustion Calibration sheet.

Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide (NOx)

Carbon Monoxide (CO)

50%

6% - 7%

<20 ppm

<100 ppm

40%

6% - 7%

<20 ppm

<100 ppm

30%

6% - 7%

<20 ppm

<100 ppm

18%

5% - 7%

<20 ppm

<100 ppm

29. If the oxygen level at the 18% valve position is too high and the Blower voltage is at the

minimum value, you can adjust the idle screw (TAC valve) which is recessed in the top of
the Air/Fuel Valve (see Figure 4-4, below). Rotate the screw 1/2 turn clockwise (CW) to
add fuel and reduce the O

2

to the specified level. Recalibration MUST be performed again

from 50% down to 14% after making a change to the idle screw (TAC valve).

30. This completes the Natural Gas combustion calibration procedures.