8 combustion cal menu, 9 bst (boiler sequencing technology ) menu – AERCO BMK 6000 User Manual
Page 47

Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0086_0D
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 47 of 210
GF-133
Ph.: 800-526-0288
03/20/14
3.8 COMBUSTION CAL MENU
The Combustion Cal (Calibration) Menu is protected by the level 2 password (6817) which must
be entered to view or change the menu items shown in Table 3-6. These menu items are used to
vary the speed of the unit’s blower motor based on air temperature and air density at prescribed
Air/Fuel Valve positions (% open). This is accomplished by providing a DC drive voltage to the
motor which adjusts the rotational speed of the blower to maximize combustion efficiency and
ensure the unit conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions
specified in Chapter 4. The valve positions (%) and default drive voltages are listed in Table 3-6.
Table 3-6: Combustion Cal Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
CAL Voltage 14%
1.70
2.70
2.20
CAL Voltage 30%
1.90
2.50
2.00
CAL Voltage 40%
1.90
3.40
2.25
CAL Voltage 50%
2.20
3.50
2.70
CAL Voltage 70%
3.20
4.40
3.95
CAL Voltage 100%
7.20
10.00
8.00
SET Valve Position
0%
100%
Variable
Blower Output
Monitor Blower Output Voltage
Set Stdby Volt
0
4.00 V
0/2.00 V
Oxygen Level
0%
25%
Variable
3.9 BST (BOILER SEQUENCING TECHNOLOGY ) MENU
The BST Menu must be Enabled in order to be displayed and accessed. The BST Enable item is
located at the end of the Configuration Menu.
The Boiler Sequencing Technology (BST) Menu contains all of the items required to Configure,
Operate and Monitor the functionality of the BST System. There are over 50 items in this menu,
and selecting any particular item from the list, for inspection or modification, could be time
consuming. As a result, the BST Menu has been segmented into FIVE logical groups based on
functionality.
The five Item groups are:
1. BST Monitor Items
2. BST SETUP MENU*
3. * OPERATE MENU *
4. *TEMP CTRL MENU*
5. *BST COMM MENU*
These displayed item groups are displayed in UPPER CASE letters, and are bounded by an
asterisk * in order to readily identify them within the item list.