Chapter 7. maintenance, 1 maintenance schedule, Chapter 7 – AERCO BMK 1500-2000 User Manual
Page 85: Maintenance
Benchmark 1500 - 2000 Boilers
CHAPTER 7 – MAINTENANCE
OMM-0097_0D
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 85 of 188
GF-142
Ph.: 800-526-0288
CHAPTER 7. MAINTENANCE
7.1 MAINTENANCE SCHEDULE
The unit requires regular routine maintenance to keep up efficiency and reliability. For best
operation and life of the unit, the following routine maintenance procedures should be performed
in the time periods specified in Table 7-1. For a complete inspection check list see ASME CSD-
1 chart.
In order to perform the maintenance tasks specified in Table 7-1, the following maintenance kits
are available through your local AERCO Sales Representative:
• 12 Month Maintenance Kit, Part No. 58025-01
• 24-Month Waterside/Fireside Inspection Kit, Part No. 58025-13 (See NOTE below)
NOTE:
The 24-Month Waterside/Fireside Inspection Kit also includes the items
contained in the Annual Maintenance Kit (58025-01). Therefore, only Kit
Part No. 58025-13 is required when performing the waterside/fireside
inspections. Refer to Appendix L for recommended spare
TO AVOID PERSONAL INJURY, PRIOR TO SERVICING ENSURE THAT
THE FOLLOWING GUIDELINES ARE STRICTLY OBSERVED:
• DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE
SWITCH AND AC SUPPLY CIRCUIT BREAKER.
• SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-OFF VALVE
PROVIDED WITH THE UNIT
• ALLOW THE UNIT TO COOL TO A SAFE WATER TEMPERATURE
TO PREVENT BURNING OR SCALDING
Table 7-1: Maintenance Schedule
Section
Item
6 Mos.
12 Mos.
24 Mos.
Labor
Time
7.2
Igniter-Injector
(66013)
*Inspect
Inspect
Replace
15 mins.
7.3
Flame Detector
(66020)
*Inspect
Inspect
Replace
15 mins.
7.4
O
2
Sensor
(61026)
*Inspect
Inspect
15 mins.
4.3
Combustion
Calibration
*Check
Check
1 hr.
7.5
Testing of Safety
Devices
See ASME CSD-1
Chart
45 mins.
7.6
Burner
Inspect
2 hrs.
7.7
Condensate
Drain Trap
*Inspect
Inspect, Clean &
Replace Gaskets
Inspect, Clean &
Replace Gaskets
30 mins.
7.8
Air Filter (59138)
Clean
Replace
15 mins.
* Only performed after initial 6 month period after initial startup.