7 tuning menu – AERCO BMK 1500-2000 User Manual
Page 42
Benchmark 1500 - 2000 Boilers
CHAPTER 3 – OPERATION
Page 42 of 188
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0097_0D
Ph.: 800-526-0288
GF-142
Table 3-4: Configuration Menu - Continued
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Max Valve Position
40%
100%
100%
Pump Delay Timer
0 min.
30 min.
0 min.
Aux Start On Dly
0 sec.
120 sec.
0 sec.
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
Low Fire Timer
2 sec.
600 sec.
2 sec.
Setpt Limiting
Enabled or Disabled
Disabled
Setpt Limit Band
0°F
10°F
0
Network Timeout
5 Sec
999 Sec
30 Sec
HI DB Setpt EN
0%
100%
30%
Demand Offsert
0
25
0
Deadband High
0
25
0
Deadband Low
0
25
0
DO NOT CHANGE the Analog Output Menu Item from its Default
setting (Valve Position 0-10V).
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by factory-trained personnel.
Table 3-5: Tuning Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Prop Band
1°F
120°F
8°F
Integral Gain
0.00
2.00
1.6
Derivative Time
0.0 min
2.00 min
0.10 min
Warmup Prop Band
0°F
120°F
95°F
Warmup Int Gain
0
2.00
0.50
Warmup PID timer
0 sec.
240 sec.
20 sec.
Reset Defaults?
Yes, No, Are You Sure?
No