Benchmark 1500 - 2000 Boilers

CHAPTER 3 – OPERATION

OMM-0097_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 45 of 188

GF-142

Ph.: 800-526-0288

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Setback Setpoint

BST Setpt Lo Limit

BST Setpt HI Limit

130°F

Setback Start

12:00am

11:59pm

12.00am

Setback End

12:00am

11:59pm

12.00am

Rate Threshold

1°F

30°F

15°F

*BST OPERATE
MENU*

Disabled

Enabled

Disabled

BST Next On VP

16%

100%

50%

BST Max Boilers

1

8

8

BST On Delay

30 sec

300 sec

60 sec

BST On Timeout

15 sec

300 sec

60 Sec

Valve Override

Off

Closed

Open

Off

Valve Off Delay

0

15 min

1 min

BST Sequencing

Run Hours

Unit Size

Select Lead

Run Hours

Select Lead Unit

0

127

0

Select Lag Unit

0

127

0

Lead/Lag Hours

25 hours

225 hours

72 hours

*BST TEMP CTRL
MENU*

Disabled

Enabled

Disabled

BST Temp Hi Limit

40°F

210°F

210°F

BST Setpt Lo Limit

40°F

BST Setpt HI Limit

60°F

BST Setpt HI Limit

BST Setpt Lo Limit

220°F

195°F

BST Prop Band

1°F

120°F

100°F

BST Intgral Gain

0.00

2.00

0.50

BST Deriv Time

0.00 Min

2.00 Min

0.10 Min

BST Deadband Hi

0

25

1

BST Deadband Lo

0

25

1

Deadband En Time

0

120 Sec

30 Sec

BST FR Up Rate

1

120

20

BST Bldg Ref Tmp

40°F

230°F

70°F

BST Reset Ratio

0.1

9.9

1.2

System Start Tmp

30°F

120°F

60°F

*BST COMM MENU*

Disabled

Enabled

Disabled

Comm Address

0

127

0

BST Min Addr

1

128

1

BST Max Addr

1

128

8

SSD Address

0

250

247

SSD Poll Control

0

1000

0