Benchmark 1500 - 2000 Boilers

CHAPTER 6 – SAFETY DEVICE TESTING

Page 80 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

Blocked Inlet Switch

Test – Continued

WARNING

THE BLOWER SUCTION IS VERY STRONG AND CAN PULL NEARBY
OBJECTS INTO THE BLOWER’S FAN BLADES. DO ALLOW ANYTHING
TO BE PULLED INTO THE BLOWER. DO NOT WEAR ANYTHING THAT
COULD GET CAUGHT AND PULL YOU INTO THE BLOWER.

3. Turn off the gas supply ball valve to the boiler and then complete the following steps:

(a) Use jumper wires to jump out the Low Gas Pressure Switch and the Blower Proof

Switch.

(b) Remove the black connector boot from the Flame Detector.

(c) Connect the Flame Signal Generator to the black connector boot.

Figure 6.3a: Connecting the Flame Signal Generator

(d) Keep the alligator clip away from bare metal parts until step 4c.

4. Complete the following with the boiler operating in Manual mode:

(a) Ramp the boiler up to 100% fire rate and then turn on the main ON/OFF switch on

the front of the Control Panel.

(b) Push the BACK button three (3) times to return to the upper level menu.

(c) When the Controller gets into the ignition phase, the Control Panel will show

IGNITION TRIAL. At that point attach the alligator clip (see Figure 6.3a) to any bare
metal surface or ground. The C-More display should now show FLAME PROVEN
and begin to ramp up to 100% fire rate. Note that no gas or flame is present in the
boiler at this time.

5. Wait for the boiler to ramp up to at least 90% before continuing.

6. Cover the combustion air inlet opening with a solid, flat object, such as a piece of

thick

plywood or a thick metal plate.

7. The unit should shut down and display AIRFLOW FAULT DURING RUN. This step

confirms proper operation of the Blocked Inlet Switch.

8. Remove the cover from the air inlet opening and reinstall the Combustion Air Duct or air

filter.

9. Remove the jumper wires installed in step 2 and replace the black connector boot on the

Flame Detector.

10. Press the CLEAR button. The unit should restart.

TO WIRE HARNESS

Flame Detector
Connector Boot

Flame Signal Generator